cabling and connections
vacon 47
Local contacts: https://www.danfoss.com/en/contact-us/contacts-list/
6
6.1.1.5
Inverter supply and motor cables , NXI_xxxx 5
Type
Enclosure
size
IL
[A]
Module supply (DC)
(per terminal)
Cu [mm2]
Motor cable
[mm2]
NXI_0168 5
FI9
170
1
) 2×(1×24)
Cu: 3×95+50
Al: 3×120+70
NXI_0205 5
205
1
) 2×(1×24)
Cu: 3×150+70
Al: 3×240Al+72Cu
NXI_0261 5
261
1
) 3×(1×24)
Cu: 3×185+95
Al: 2×(3×120+70)
NXI_0300 5
300
1
) 6×(1×24)
Cu: 2×(3×120+70)
Al: 2×(3×185Al+57Cu)
NXI_0385 5
FI10
385
2
) 5×40
Cu: 2×(3×120+70)
Al: 2×(3×185Al+57Cu)
NXI_0460 5
460
2
) 5×40
Cu: 2×(3×150+70)
Al: 2×(3×240Al+72Cu)
NXI_0520 5
520
2
) 6×40
Cu: 2×(3×185+95)
Al: 2×(3×300Al+88Cu)
NXI_0590 5
3
) FI12
590
2
) 5×40
Cu: 2×(3×240+120)
Al: 4×(3×120Al+41Cu)
NXI_0650 5
650
2
) 5×40
Cu: 4×(3×95+50)
Al: 4×(3×150Al+41Cu)
NXI_0730 5
730
2
) 5×40
Cu: 4×(3×120+70)
Al: 4×(3×185Al+57Cu)
NXI_0820 5
820
2
) 5×40
Cu: 4×(3×150+70)
Al: 4×(3×185Al+57Cu)
NXI_0920 5
920
2
) 5×40
Cu: 4×(3×150+70)
Al: 4×(3×240Al+72Cu)
NXI_1030 5
1030
2
) 6×40
Cu: 4×(3×185+95)
Al: 4×(3×300Al+88Cu)
NXI_1150 5
FI13
1150
2
) 5×40
Cu: 4×(3×240+170)
Al: 6× (3×185Al+57Cu)
NXI_1300 5
1300
2
) 5×40
Cu: 6×(3×150+70)
Al: 6× (3×240Al+72 Cu)
NXI_1450 5
1450
2
) 6×40
Cu: 6×(3×185+95)
Al: 6× (3×240Al+72 Cu)
NXI_1770 5
3
) FI14
1770
2
) 5×40
Cu: 2× 4×(3×240+170)
Al: 2× 6× (3×185Al+57Cu)
NXI_2150 5
2150
2
) 5×40
Cu: 2× 6×(3×150+70)
Al: 2× 6× (3×240Al+72 Cu)
NXI_2700 5
2700
2
) 6×40
Cu: 2× 6×(3×185+95)
Al: 2× 6× (3×240Al+72 Cu)
Note:
1
) Flexible conductor. Min. temperature endurance for isolation 70°C
2
) Copper Busbar
3
) The modules requires symmetrical parallel cable with min length 40m or dU/dt- or sinus filter.
Table valid for enclosure class IP20 cabinets
Motor cables:
EN 60204-1, IEC 60364-5-2/2001
-
PVC insulation
-
40 °C ambient temperature
-
70 °C surface temperature
Table 6
-
4. Cable sizes for VACON
®
NX_5