background image

Actual value special display 

 
The 

Actual value special display

 parameters are used to convert and display the actual value signal 

in a form more informative to the user. 
 
The Actual value special display parameters are available in 

PID Control Application 

and 

Pump and 

Fan Control Application:

 

 

Par ID 

Parameter name 

Parameter code in 

PID ctrl applic. 

Parameter code in 

Pump&Fan ctrl applic.

ID1033 

Actual value special display minimum 

2.2.46 2.9.29 

ID1034 

Actual value special display maximum 

2.2.47 2.9.30 

ID1035 

Actual value special display decimals 

2.2.48 2.9.31 

ID1036 

Actual value special display unit 

2.2.49 2.9.32 

 

Example: 
 
The actual value signal sent from a sensor (in mA) represents the amount of waste water pumped 
from a tank per second. The signal range is 0(4)…20mA. Instead of receiving the level of the actual 
value signal (in mA) on the display, you wish to receive the amount of water pumped in m

3

/s. You 

then set a value for par. ID1033 to correspond to the minimum signal level (0/4 mA) and another 
value for par. ID1034 to correspond to the maximum signal level (20 mA). The number of decimals 
needed can be set with par. ID1035 and the unit (m

3

/s) with par. ID1036. The level of the actual value 

signal is then scaled between the set min and max values and displayed in the selected unit. 
 
The following units can be selected (par. ID1036): 
 

Value 

Unit 

On keypad 

Value 

Unit 

On keypad 

Not Used 

 

15 

m3 /h 

m3/h 

16 

°

°

°

°

17 

ft ft 

m m 

18 

gal / s 

GPS 

bar bar 

19 

gal / min 

GPM 

mbar mbar 

20 

gal / h 

GPH 

Pa Pa 

21 

ft3 / s 

CFS 

kPa kPa 

22 

ft3 / min 

CFM 

PSI PSI 

23 

ft3 / h 

CFH 

m / s 

m/s 

24 

A A 

10 

l / s 

l/s 

25 

V V 

11 

l / min 

l/m 

26 

W W 

12 

l / h 

l/h 

27 

kW kW 

13 

m3 /s 

m3/s 

28 

Hp Hp 

14 

m3 /min 

m3/m 

 

 

 

 
NOTE: The maximum number of characters that can be shown on keypad is 4. This means that in 
some cases the display of the unit on the keypad does not comply with the standards. 

Отзывы: