2.4.3
INPUT SIGNALS (CONTROL KEYPAD: MENU M2 -> G2.2)
Table 6: Input signals, G2.2
Index
Parameter
Min
Max
Unit
Default
Cust
ID
Description
P2.2.1
Start/Stop logic
0
6
0
300
Logic = 0
Ctrl sgn 1 = Start
forward
Ctrl sgn 2 = Start
reverse
Logic = 1
Ctrl sgn 1 = Start/
Stop
Ctrl sgn 2 = Reverse
Logic = 2
Ctrl sgn 1 = Start/
Stop
Ctrl sgn 2 = Run ena-
ble
Logic = 3
Ctrl sgn 1 = Start
pulse (edge)
Ctrl sgn 2 = Stop
pulse
Logic = 4
Ctrl sgn 1 = Forward
pulse (edge)
Ctrl sgn 2 = Reverse
pulse (edge)
Logic = 5
Ctrl sgn 1 = Start
pulse (edge)
Ctrl sgn 2 = Reverse
pulse
Logic = 6
Ctrl sgn 1 = Start
pulse (edge)
Ctrl sgn 2 = Enable
pulse
VACON · 26
STANDARD APPLICATION
2
TEL. +358 (0)201 2121 · FAX +358 (0)201 212 205