6.4.12
NXP DRIVES: MASTER FOLLOWER PARAMETERS (CONTROL KEYPAD: MENU M2 -
> G2.11)
Table 82: Master Follower parameters, G2.5
Index
Parameter
Min
Max
Unit
Default
Cust
ID
Description
P2.11.1
Master Follower
mode
0
2
0
1324
0 = Single drive
1 = Master drive
2 = Follower drive
P2.11.2
Follower stop
function
0
2
2
1089
0 = Coasting
1 = Ramping
2 = As Master
P2.11.3
Follower speed
reference select
0
18
18
1081
0 = AI1
1 = AI2
2 = AI1+AI2
3 = AI1-AI2
4 = AI2-AI1
5 = AI1xAI2
6 = AI1 Joystick
7 = AI2 Joystick
8 = Keypad
9 = Fieldbus
10 = Motor poten-
tiometer
11 = AI1, AI2 mini-
mum
12 = AI1, AI2 maxi-
mum
13 = Max fre-
quency
14 = AI1/AI2 selec-
tion
15 = Encoder 1 (C.
1)
16 = Encoder 2 (C.
3)
17 = Master Refer-
ence
18 = Master Ramp
Out