Table 38: Drive control parameters, G2.4
Index
Parameter
Min
Max
Unit
Default
Cust
ID
Description
P2.4.10
Frequency to start
DC braking during
ramp stop
0.10
10.00
Hz
1.50
515
P2.4.11
DC braking time
at start
0.00
600.00
s
0.00
516
0 = DC brake is off
at start
P2.4.12 *
Flux brake
0
1
0
520
0 = Off
0 = On
P2.4.13
Flux braking cur-
rent
0.00
I
L
A
I
H
519
5.4.6
PROHIBIT FREQUENCY PARAMETERS (CONTROL KEYPAD: MENU M2 -> G2.5)
Table 39: Prohibit frequency parameters, G2.5
Index
Parameter
Min
Max
Unit
Default
Cust
ID
Description
P2.5.1
Prohibit frequency
range 1 low limit
-1.00
320.00
Hz
0.00
509
0 = Not used
P2.5.2
Prohibit frequency
range 1 high limit
0.00
320.00
Hz
0.00
510
0 = Not used
P2.5.3
Prohibit frequency
range 2 low limit
0.00
320.00
Hz
0.00
511
0 = Not used
P2.5.4
Prohibit frequency
range 2 high limit
0.00
320.00
Hz
0.00
512
0 = Not used
P2.5.5
Prohibit frequency
range 3 low limit
0.00
320.00
Hz
0.00
513
0 = Not used
P2.5.6
Prohibit frequency
range 3 high limit
0.00
320.00
Hz
0.00
514
0 = Not used
P2.5.7
Prohibit acc./dec.
ramp
0.1
10.0
x
1.0
518
VACON · 116
PID CONTROL APPLICATION
5
TEL. +358 (0)201 2121 · FAX +358 (0)201 212 205
Содержание NX series
Страница 1: ...vacon nx ac drives all in one application manual ...
Страница 2: ......
Страница 5: ...VACON 5 24 HOUR SUPPORT 358 0 201 212 575 EMAIL VACON VACON COM ...
Страница 6: ...VACON 6 TEL 358 0 201 2121 FAX 358 0 201 212 205 ...
Страница 391: ......