4 • va c o n
t ec h ni c a l d at a
Tel. +358 (0)201 2121 • Fax: +358 (0)201 2121 205
2
2.2
Pr ofibus cabl e
1. Pr ofibus devices ar e connected in a bus str uctur e. Up to 32 stations (master or sl aves) can
be connected in one segm ent. The bus is ter minated by an active bus ter minator at the be-
ginning and end of each segment (see
). To ensur e er r or - fr ee oper ation, both bus
ter minations must al ways be power ed. When mor e than 32 stations ar e used, r epeater s
(line ampl ifier s) must be used to connect the individual bus segments.
The maximum cabl e length depends on the tr ansmission speed and cabl e type (see
Table 2- 3). The
specified cabl e length can be incr eased using the r epeater s. The use of mor e than 3 r epeat er s in se-
r ies is not r ecom mended.
Par am eter
Line A
Line B
Im pedance
Capacit y
Resist ance
Wir e gauge
Conduct or ar ea
135 ... 165
(3 to 20 Mhz)
< 30 pF/m
< 110
/ km
> 0.64 mm
> 0.34 mm
2
100 ... 130
( f > 100kHz)
< 60 pF/m
-
> 0.53 mm
> 0.22 mm
2
Table 2- 2. Line par ameter s
Baud r at e
(kbit / s)
9.6
19.2
93.75
187.5
500
1500
3000-
12000
Lengt h l ine A (m )
1200
1200
1200
1000
400
200
100
Lengt h l ine B
(m )
1200
1200
1200
600
200
-
-
Table 2- 3. Line length for differ ent tr ansmission speeds
E.g. fol lowing cabl es can be used:
Bel den
Pr ofibus
Data
Cable
3079A
Ol fl ex
Pr ofibus
Cable
21702xx
Siem ens
SINEC
L2
LAN
cable
for
Pr ofibus
6XV1
830- 0AH10
NOTE!
2. Minimum distance between power and bus cabl es is 30 cm.
3. Minimum cabl e length of 1 m between two stations is r ecommended.