c o mmi ssi o n i n g
va c o n • 2 5
24- hour suppor t: +358 (0)201 212 575 • Email: [email protected]
6
#
Nam e
Defaul t
Range
Descr iption
1
SLAVE ADDRESS
126
2…126
2
BAUD RATE
10 (=AUTO)
1 - 9.6 kBaud
2 - 19.2 kBaud
3 - 93.75 kBaud
4 - 187.5 kBaud
5 - 500 kBaud
6 - 1.5 Mbaud
7 - 3 MBaud
8 - 6 Mbaud
9 - 12 Mbaud
10 – AUTOMATIC
Communication speed in baud
3
PPO TYPE
1 - PPO1
2 - PPO2
3 - PPO3
4 - PPO4
5 - PPO5
Par ameter , CW/SW, Ref/Act
Par ameter , CW/ SW, Ref/Act, PD1- PD4
CW/SW, Ref/Act
CW/SW, Ref/Act, PD1- PD4
Par ameter , CW/ SW, Ref/Act, PD1- PD8
4
OPERATE MODE
1 – PROFIDRIVE
2 – BYPASS
3 – ECHO
Use mode ” PROFIDRIVE” with standard
applications
Table 6- 1. Pr ofibus par ameter s
The par am eter s of ever y device must be set befor e connecting to the bus. Especial ly the par ameter s
“ SLAVE ADDRESS” and “ PPO TYPE” must be the same as in the master configur ation.
Profibus status
To see the pr esent status of the Pr ofibus fieldbus, enter the
Pr ofibus status page from Monitor menu
(G7.5.2). See
Figur e 6- 2 and Table 6- 2 bel ow.
Figur e 6- 2. Pr ofibus status
Pr ofibus status
0
Waiting par ameter fr om Master
1
Waiting configur ation fr om Master
2
Communication establ ished
Table 6- 2. Pr ofibus status indications
Monitor
READY
I/Oterm
V1
V1
Profibus status
READY
I/Oter m
2516.0
Message counter
Profibus status