7.9.2
DIN ID Control
This function is used to control any parameter between two different values with a digital input.
Different values are given for DI LOW and DI HIGH.
SEL
G
IN 0
IN 1
DI
ID Control Digital Input
P
Value for LOW
P
Value for High
P
DIN Controlled ID
Figure 4.
P2.9.2.1
ID Control Digital Input ID1570
P2.9.3.1
ID Control Digital Input ID1590
P2.9.4.1
ID Control Digital Input ID1578
Select a digital input to be used for controlling the parameter selected by ID1571.
P2.9.2.2
DIN Controlled ID
ID1571
P2.9.3.2
DIN Controlled ID
ID1575
P2.9.4.2
DIN Controlled ID
ID15719
Select a parameter ID controlled by ID1570.
P2.9.2.3
Value for Low digital input (FALSE)
ID1572
P2.9.3.3
Value for Low digital input (FALSE)
ID1592
P2.9.4.3
Value for Low digital input (FALSE)
ID15794
Set the controlled parameter value when the digital input (ID1570) is LOW for the
parameter selected by ID1571. The function does not recognise decimals. For example,
give the value 10.00 Hz as
1000
.
P2.9.2.4
Value for High digital input (TRUE)
ID1573
P2.9.3.4
Value for High digital input (TRUE)
ID1593
P2.9.4.4
Value for High digital input (TRUE)
ID1596
Set the controlled parameter value when the digital input (ID1570) is HIGH for the
parameter selected by ID1571. The function does not recognise decimals. For example,
give the value 10.00 Hz as
1000
.