apfiff09 marine
VACON®
•
127
Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
Classified as Public
7.2.7 Adjust Reference
Adjust reference function is used to fine tune the main reference. Adjust reference is added to main
refe
rence after “SpeedShare” function.
F
Analogue Input 1
F
Analogue Input 2
F
Analogue Input 4
F
Analogue Input 3
F
FB Adjust Reference
C
10000
P
Adjust Max
P
Adjust Min
FW
FreqRef1
MULDIV
VALUE
MULTIP
DIVIS
MULDIV
VALUE
MULTIP
DIVIS
ADD
+
+
+
C
1000
F
Adjust Reference
F
Not Used
P
Adjust Input
MUX
K
IN 0
IN 1
IN 2
IN 3
IN 4
IN 5
SUB
IN 1
IN 2
P
Adjust Min
P2.2.12.1 Adjust input
ID493
“Adjust Input”
With this parameter you can select the signal according to which the frequency reference
to the motor is fine adjusted.
0
Not used
1
Analogue input 1
2
Analogue input 2
3
Analogue input 3
4
Analogue input 4
5
FB Adjust Reference ID47 Monitoring Signal
P2.2.12.2 Adjust minimum
ID494
“Adjust minimum”
Percentage that is subtracted from the main reference when adjust input is at minimum.
P2.2.12.3 Adjust maximum
ID495
“Adjust Maximum”
These parameters define the minimum and maximum of adjusted signals.
Input Reference [Hz]
Reference [Hz]
Ajust Min 10 %
Ajust Max 10 %
25,0 Hz
27,5 Hz
22,5 Hz
Adjust input
If the minimum and maximum are not equal to zero, the adjustment is not at the
middle point of the analogue input or at zero point if -10...+10 Vdc input is used. In the
below picture, the minimum is 20% and the maximum 10%.