Filter types
vacon • 23
Local contacts: https://www.danfoss.com/en/contact-us/contacts-list/
There are enclosure restrictions and details for selection and mounting when using UL listed
accessories, IP00 dU/dt-filter models. These restrictions and details should be noted during the
filter assembly. For details of drive selection and enclosure restrictions, see Table 15.
• Suitable for use on a circuit capable of delivering not more than 100 000 rms symmetrical
amperes, 600 V maximum, or equivalent.
• Use 60/75 C CU wire only or equivalent copper/aluminum busbars.
• Tightening torque and wire range for field wiring terminals are mentioned in the manual or
on the wiring diagram.
Table 15. Drive suitability table and details of enclosure restrictions for UL listed accessories dU/dt
filters
Illustration figures are shown in Chapter 3.2.
Filter, IP00 class, UL listed
accesories
Compatible VACON
®
NX drive
enclosure sizes
Figures of the enclosure and
quantity of dU/dt filters in the
same enclosure
DUT-0012-6-0
FR4, FR6
No enclosure restrictions
DUT-0025-6-0
FR4, FR5, FR6
DUT-0055-6-0
FR5, FR6, FR7
Figures 30, 31, 34 1-2 pcs
DUT-0080-6-0
FR6, FR7, FR8
DUT-0130-6-0- P-UL
FR7, FR8, FR9, FI9
DUT-0210-6-0- P-UL
FR7, FR8, FR9, FI9
DUT-0280-6-0- P-UL
FR8, FR9, FR10, FR11, FR12, FI9,
FI10, FI12
Figures 30, 31, 33 1-2 pcs
DUT-0350-6-0- P-UL
FR8, FR9, FR10, FR11, FR12, FI9,
FI10, FI12
DUT-0420-6-0- P-UL
FR9, FR10, FR11, FR12, FI10, FI12
DUT-0600-6-0- P-UL
FR9, FR10, FR11, FR12, FI10, FI12
DUT-0820-6-0- P-UL
FR10, FR11, FI13, FI14
Figures 32 and 35, 1 pcs
DUT-1200-6-0- P-UL
FI13, FI14, FR13, FR14
DUT-1500-6-0- P-UL
FI13, FI14, FR13, FR14
Содержание 640-974
Страница 1: ...vacon nx ac drives rfi du dt and sine filters user manual ...
Страница 2: ......