77
vacon
vacon 50x parameters
Tel. +358 (0)201 2121 • Fax +358 (0)201 212205
7
Cin F-Motor
Cin analog input sets the FWD motoring current limit value,
range 0–200%
NOTE: Current limit is only available when Parameter 501 is set to Linear Auto. If Param-
eter 501 is set to Vector, then the Current Limiting values will actually be Torque Limiting
values.
This parameter sets the current limiting point when the drive is in motoring mode in the
forward direction. The limit is expressed as a percentage of the current capacity of the
drive.
This parameter sets the current limiting point when the drive is in motoring mode in the
reverse direction. The limit is expressed as a percentage of the current capacity of the
drive.
This parameter sets the current limiting point when the drive is in regenerative mode in
the forward direction. The limit is expressed as a percentage of the current capacity of
the drive.
This parameter sets the current limiting point when the drive is in regenerative mode in
the reverse direction. The limit is expressed as a percentage of the current capacity of
the drive.
This parameter sets the frequency where current limit becomes active. This value will
also be the frequency point the drive will decelerate the motor to during Motoring Current
Limit.
This parameter determines the ramp rate when the drive enters Current Limit, and de-
fines the ramping rate of the drive when in a current limiting mode. If the drive is in re-
generative current limit, it is an acceleration time. If the drive is in motoring current limit,
it is a deceleration time.
This parameter limits the lowest amount of current (or Torque) limiting that can occur
when the limit threshold is determined by an analog input.
601 Cur Lim Mtr Fwd
Default: 120%
Range: 5–150%
Level 2
602 Cur Lim Mtr Rev
Default: 120%
Range: 5–150%
Level 2
603 Cur Lim Reg Fwd
Default: 80%
Range: 5–150%
Level 2
604 Cur Lim Reg Rev
Default: 80%
Range: 5–150%
Level 2
605 Cur Lim Freq
Default: 3.0 Hz
Range: 0.0–400.0 Hz
Level 2
606 Ramp Time CL
Default: 1.0 sec
Range: 0.1–3200.0 sec
Level 2
607 Cur Lim Minimum
Default: 10%
Range: 0–50%
Level 2
Содержание 50X
Страница 1: ......
Страница 5: ...introduction vacon 4 24 hour support 358 0 40 837 1150 Email vacon vacon com 1 ...
Страница 23: ...receiving and installation vacon 22 24 hour support 358 0 40 837 1150 Email vacon vacon com 3 ...
Страница 30: ...29 vacon connections Tel 358 0 201 2121 Fax 358 0 201 212205 4 Figure 11 Power Terminals Size 4 and 5 ...
Страница 39: ...connections vacon 38 24 hour support 358 0 40 837 1150 Email vacon vacon com 4 ...
Страница 49: ...keypad operation and programming vacon 48 24 hour support 358 0 40 837 1150 Email vacon vacon com 5 ...
Страница 59: ...using macro mode and getting a quick start vacon 58 24 hour support 358 0 40 837 1150 Email vacon vacon com 6 ...
Страница 101: ...vacon 50x parameters vacon 100 24 hour support 358 0 40 837 1150 Email vacon vacon com 7 ...
Страница 107: ...hexadecimal to binary conversion vacon 106 24 hour support 358 0 40 837 1150 Email vacon vacon com 9 ...
Страница 113: ...eu declaration of conformity vacon 112 24 hour support 358 0 40 837 1150 Email vacon vacon com 11 ...
Страница 131: ...summary of vacon 50x parameters vacon 130 24 hour support 358 0 40 837 1150 Email vacon vacon com 12 ...
Страница 132: ......