Communications
vacon • 15
Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
6
NOTE!
2004 - 2007 can set as PID Control Reference by setting P15.1(Setpoint selection) or PID
Actual value by setting P15.4 (Feedback value selection)!
2004 - 2007 can be set as the Analogue Output by P9.1, P9.5, P9.9.
2004 - 2008 can set as Aux Control Word with P10.9:
b0: Run enable
b1: acc / dec ramp 2 selection
b2: freq reference 2 selection
NOTE!
•
AUX CW is active when configured, even if control place is not the fieldbus
•
b0 Run enable is computed in AND with a possible Run enable signal from digital input. Fall
of enable will cause coasting stop.
Status word (output process data)
Information about the status of the device and messages is indicated in the Status word. The Status
word is composed of 16 bits the meanings of which are described in the table below:
Table 9. Input process data
ID
Modbus register
Name
Scale
Type
2001
32001, 42001
FB Control Word
Binary coded
2002
32002, 42002
FB General Control Word
Binary coded
2003
32003, 42003
Actual speed
0.01
%
2004
32004, 42004
Programmable by P10.9
2005
32005, 42005
Programmable by P10.9
2006
32006, 42006
Programmable by P10.9
2007
32007, 42007
Programmable by P10.9
2008
32008, 42008
Programmable by P10.9
2009
32009, 42009
-
-
-
2010
32010, 42010
-
-
-
2011
32011, 42011
-
-
-
Table 10. Status word (output process data)
Bit
Description
Value = 0
Value = 1
B0, RDY
Drive not ready
Drive ready
B1, RUN
Stop
Run
B2, DIR
Clockwise
Counter-clockwise
B3, FLT
No fault
Fault active
B4, W
No alarm
Alarm active
B5, AREF
Ramping
Speed reference reached
B6, Z
-
Drive is running at zero speed
B7 - B15
-
-