3.1.2 Cooling
Enough free space shall be left above and below the frequency converter to ensure
sufficient air circulation and cooling. You will find the required dimensions for free
space in the table below.
If several units are mounted above each other the required free space equals C + D
(see figure below). Moreover, the outlet air used for cooling by the lower unit must
be directed away from the air intake of the upper unit.
The amount of cooling air required is indicated below. Also make sure that the tem-
perature of the cooling air does not exceed the maximum ambient temperature of
the converter.
*. Min clearance A and B for drives for
MI1 ~ MI3 can be 0 mm if the ambient
temperature is below 40 degrees.
Figure 3.12: Installation space
A = clearance around the freq. converter (see also B)
B = distance from one frequency converter to another or distance to cabinet wall
C = free space above the frequency converter
D = free space underneath the frequency converter
NOTE!
See the mounting dimensions on the back of the drive.
Leave
free space
for cooling above
(100 mm)
, below
(50 mm)
, and on the sides
(20 mm)
of Vacon 20! (For MI1 - MI3, side-to-side installation allowed only if the ambient tem-
perature is below 40 °C; For MI4-MI5, side-to-side installation is not allowed.
Min clearance (mm)
Type
A*
B*
C
D
MI1
20
20
100
50
MI2
20
20
100
50
MI3
20
20
100
50
MI4
20
20
100
100
MI5
20
20
120
100
Table 3.4: Min. clearances around AC drive
Type
Cooling air required (m³/h)
MI1
10
MI2
10
MI3
30
MI4
45
MI5
75
Table 3.5: Required cooling air
B
C
B
A
D
A
Содержание 20
Страница 1: ...vacon 20 ac drives complete user manual ...
Страница 2: ......
Страница 6: ...1 ...
Страница 12: ...6 vacon safety 1 ...
Страница 20: ...14 vacon installation 3 Figure 3 7 Flange mounting depth dimensions for MI4 and MI5 Unit mm MI5 MI4 ...
Страница 27: ...installation vacon 21 3 ...
Страница 28: ...22 vacon installation 3 MI1 MI5 3P 230 V POWER LOSS ...
Страница 29: ...installation vacon 23 3 ...
Страница 30: ...24 vacon installation 3 ...
Страница 31: ...installation vacon 25 3 MI1 MI3 1P 230 V POWER LOSS ...
Страница 32: ...26 vacon installation 3 ...
Страница 40: ...34 vacon installation 3 Figure 3 23 Open the lid MI1 MI3 Figure 3 24 Open the lid MI4 MI5 ...
Страница 43: ...installation vacon 37 3 4 5 6 ...
Страница 52: ...46 vacon installation 3 ...
Страница 76: ...70 vacon control panel 7 ...
Страница 104: ...98 vacon parameters 8 ...
Страница 152: ...146 vacon parameter descriptions 9 ...
Страница 158: ...152 vacon technical data 10 ...
Страница 159: ......
Страница 160: ...Rev E2 Document ID ...