32
•
vacon
monitoring & parameters
5
5.7 Digital inputs (Control panel: Menu PAR -> P5)
Code
Parameter
Min
Max
Unit Default
ID
Note
P5.1 I / O control signal 1
0
Varies
1
403
0
= Not used
1
= DI1
2
= DI2
3
= DI3
4
= DI4
5
= DI5
6
= DI6
7
= DIE1
8
= DIE2
9
= DIE3
10
= DIE4
11
= DIE5
12
= DIE6
P5.2 I / O control signal 2
0
Varies
2
404 See 5.1
P5.3
Reverse
0
Varies
0
412 See 5.1
P5.4
Ext. fault Close
0
Varies
6
405 See 5.1
P5.5
Ext. fault Open
0
Varies
0
406 See 5.1
P5.6
Fault reset
0
Varies
3
414 See 5.1
P5.7
Run enable
0
Varies
0
407 See 5.1
P5.8
Preset speed B0
0
Varies
4
419 See 5.1
P5.9
Preset speed B1
0
Varies
5
420 See 5.1
P5.10
Preset speed B2
0
Varies
0
421 See 5.1
P5.11
Ramp time 2 selec-
tion
0
Varies
0
408 See 5.1
P5.12
Motor potentiome-
ter up
0
Varies
0
418 See 5.1
P5.13
Motor potentiome-
ter down
0
Varies
0
417 See 5.1
P5.14
Remote control
place 2
0
Varies
0
425
Activates control place 2
See 5.1
P5.15
Remote control
plece freq refer-
ence 2
0
Varies
0
343
Activates control place 2
See parameter 5.1
Table 10: Digital inputs
Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: [email protected]
Содержание 20 SERIES
Страница 2: ...Buy www ValinOnline com Phone 844 385 3099 Email CustomerService valin com...
Страница 4: ...2 vacon safety 1Buy www ValinOnline com Phone 844 385 3099 Email CustomerService valin com...
Страница 15: ...installation vacon 13 2 4 5 6 Buy www ValinOnline com Phone 844 385 3099 Email CustomerService valin com...
Страница 16: ...14 vacon installation 2 Buy www ValinOnline com Phone 844 385 3099 Email CustomerService valin com...
Страница 22: ...20 vacon navigation startup 4Buy www ValinOnline com Phone 844 385 3099 Email CustomerService valin com...
Страница 52: ...50 vacon monitoring parameters 5Buy www ValinOnline com Phone 844 385 3099 Email CustomerService valin com...
Страница 54: ...52 vacon FAULT TRACING 6Buy www ValinOnline com Phone 844 385 3099 Email CustomerService valin com...