Parameter description
vacon • 58
Service support: find your nearest Vacon service center at www.vacon.com
4
4.7
Supervisions
P7.1
F
REQUENCY
SUPERVISION
1
0:No supervision
1:Low limit
2: High limit
P7.2
F
REQUENCY
SUPERVISION
VALUE
1
Threshold value for frequency supervision.
P7.3
C
URRENT
SUPERVISION
VALUE
Threshold value for current supervision.
P7.4
A
NALOG
I
N
S
UPV
S
IGNAL
0:AI1
1:AI2
P7.5
A
NALOG
I
N
S
UPV
ON
LEVEL
Output goes high when AI is higher than this value.
P7.6
A
NALOG
I
N
S
UPV
OFF
LEVEL
Output goes low when AI is lower than this value.
P7.10 P
ROCESS
S
OURCE
S
ELECT
Monitor V1.24 can show a process value, proportional to a variable measured by the drive.
Source variables are:
0: PID actual value (max: 100%)
1: output frequency (max: Fmax)
2: motor speed (max: Speed at Fmax)
3: motor torque (max: Tnom)
4: motor power (max: Pnom)
5: motor current (max: Inom)
P7.11 P
ROCESS
V
AL
D
ECIM
D
IGITS
Number of decimals shown on monitor V1.24 and also on parameter P7.12.
P7.12 P
ROCESS
M
AX
V
ALUE
Value shown on V1.24 when source variable is at its maximum. Proportionality is kept if the
source overtakes the maximum.