vacon • 15
Description of Groups
3
3.2
Monitor group: menu MON
VACON
®
20 CP/X AC drive provides you with a possibility to monitor the actual values of pa-
rameters and signals as well as statuses and measurements. See Table in which the basic
monitoring values are presented.
3.2.1
Drive Monitors
Code
Monitoring value
Unit
ID
Description
V1.1
Output frequency
Hz
1
Output frequency to motor
V1.2
Frequency reference
Hz
25
Frequency reference to motor control
V1.3
Motor shaft speed
rpm
2
Motor speed in rpm
V1.4
Motor Current
A
3
V1.5
Motor Torque
%
4
Calculated shaft torque
V1.6
Motor Power
%
5
Total power consumption of AC drive
V1.7
Motor Voltage
V
6
V1.8
Motor temperature
%
9
Calculated motor temperature
V1.9
DC-link voltage
V
7
V1.10
Unit temperature
°C
8
Heatsink temperature
V1.11
Board temperature
°C
1825
Power board temperature
V1.12
Analogue input 1
%
13
Analogue input AI1
V1.13
Analogue input 2
%
14
Analogue input AI2
V1.14
Analogue output
%
26
Analogue output
V1.15
DI1, DI2, DI3
15
Digital inputs status
V1.16
DI4, DI5, DI6
16
Digital inputs status
V1.19
RO1, RO2, DO
17
Digital outputs status
V1.21
Process variable
29
Scaled process variable See P7.10
V1.22
PID setpoint
%
20
V1.23
PID feedback
%
21
V1.24
PID error value
%
22
V1.25
PID output
%
23
V1.26
Actual Flow
litres/
min
1956
Actual flow, measured by transducer defined
in P15.1
V1.27
Volume counter 1*
m
3
1955
Cumulative water volume counter.
V1.28
Volume counter 2*
m
3
x10
4
1962
Cumulative water volume counter.
Table 3: Monitor values.
NOTE!
Values V1.22-25 are hidden when PID output is not used as frequency reference.
NOTE!
* The total volume of water in [m
3
] is given by: V1.27 + (V1.28 x 10000).