VACON® 100 X - Heater (arctic option)

vacon • 1

Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/

1

1.

VACON

®

 100 X - H

EATER

 (

ARCTIC

 

OPTION

)

Document code: DPD01097C

1.1

Safety

This manual contains clearly marked cautions and warnings which are intended for your personal 
safety and to avoid any unintentional damage to the product or connected appliances.

Please read the information included in dangers carefully. 

The optional heater allows the drive to operate in low temperature conditions down to -40°C. This
option is intended to be installed inside the drive. 

Only VACON

®

 authorized, trained and qualified personnel are allowed to install and maintain this 

component.

1.2

Dangers

1.3

Technical data

The  optional heater  has  to  be  supplied  with  single-phase  230V.  The thermal element is always
supplied  and if the drive is connected at -40°C the drive will be heated up until the temperature of
-10°C is exceeded. The heating is temperature controlled and an internal fan ensures that the air
is equally distributed inside the enclosure. 

The integrated relay output (switching capacity: 24VDC / 3A, 277VAC / 3A) can be used to control the
power-up of the drive. The contact is closed when the internal temperature is higher than the min-
imum allowed value for the power-up (~ -10°C). This can be included and managed in the logic of
the entire system.  A bi-color LED (on the enclosure of this option), shows the status of the drive,
ready or not-ready. 

Table 1. Dangers

The  components  of  the  optional heater  are  live  when  the element is con-
nected to mains potential. Coming into contact with this  voltage  is  extremely
dangerous  and  may  cause  death  or severe injury. 

The heater can be used only inside the drive and in combination with only the

VACON

®

  100  X.  Before  connecting  the  heater  to  mains,  make  sure  that  the

VACON

®

 100 X drive is closed firmly. 

Table 2. Technical information on input and relay terminals.

Heater connections

Terminal

Signal

Technical information

L1

Line

Supply voltage input terminals:
1AC 230V 50Hz 60 Hz
900 mA
Tolerance: 208V -15%... 250V +10%
External fuse needed: 

class T ( UL& CSA) min. 300V 

class J ( UL& CSA) min. 300V

N

Neutral