Startup
vacon • 22
Service support: find your nearest Vacon service center at www.vacon.com
3
3.2.6
Motor potentiometer application
Use the Motor potentiometer application for the processes where the frequency reference of
the motor is controlled (that is, increased and decreased) through digital inputs.
In this application, the I/O terminal is set to the default control place. the start/stop commands
are given with DI1 and DI2. The frequency reference of the motor is increased with DI5 and de-
creased with DI6.
It is possible to configure all the drive outputs freely in all the applications. There are 1 ana-
logue output (Output Frequency) and 3 relay outputs (Run, Fault, Ready) available on the basic
I/O board.
3.2.6.1
M1.36 Motor Potentiom
Table 7. Motor Potentiom start-up wizard menu
Code
Parameter
Min
Max
Unit
Default
ID
Description
P1.36.1
MotPot ramp time
0.1
500.0
Hz/s
10.0
331
Rate of change in the motor
potentiometer reference
when increased or
decreased with parameters
P3.3.4.1 or P3.3.4.2.
P1.36.2
MotPot Reset
0
2
1
367
Motor potentiometer fre-
quency reference reset
logic.
0 = No reset
1 = Reset if stopped
2 = Reset if powered down
P1.36.3
Preset Freq 1
P1.3
P1.4
Hz
20.0
105
Make the selection of a
preset frequency with
the digital input DI4
and DI5.
Содержание 100X series
Страница 1: ...vacon 100 x ac drives Solar pump application manual ...
Страница 2: ......
Страница 6: ...vacon 3 Vacon 100X Solar Pump Application 1 ...
Страница 8: ...2 vacon 5 Safety ...
Страница 59: ...User Interfaces vacon 56 Service support find your nearest Vacon service center at www vacon com 4 ...
Страница 160: ...vacon 157 Parameters 6 ...
Страница 169: ...Fault vacon 166 Service support find your nearest Vacon service center at www vacon com 7 ...
Страница 170: ...7 vacon 167 Fault ...
Страница 171: ......