Parameters
vacon • 136
Service support: find your nearest Vacon service center at www.vacon.com
6
AO1 M
IN
S
CALE
P3.5.4.1.5
AO1 M
AX
S
CALE
These parameters can be used to freely adjust the analogue output signal scaling. The scale is
defined in process units and it depends on the selection of parameter P3.5.4.1.1.
Example:
The drive’s output frequency is selected for the content of the analogue output signal
and parameters P3.5.4.1.4 and P3.5.4.1.5 are set to 10…40 Hz.
When the drive’s output frequency changes between 10 and 40 Hz the analogue output signal
changes between 0…20 mA.
Figure 41. AO1 signal scaling
18
Fieldbus Process Data In 7
Fieldbus Process Data In 7 from 0…10000 (corresponding
0…100.00%).
19
Fieldbus Process Data In 8
Fieldbus Process Data In 8 from 0…10000 (corresponding
0…100.00%).
Table 124. AO1 signal scaling
Selection
Selection name
Description
0 Hz
[Hz ]
[%]
0%
100%
50%
0 mA
20 mA
10 mA
10 Hz
40 Hz
9249.emf
Max freq
reference
Output
frequency
Analog
output signal
AO min
scale
AO max
scale
Содержание 100X series
Страница 1: ...vacon 100 x ac drives Solar pump application manual ...
Страница 2: ......
Страница 6: ...vacon 3 Vacon 100X Solar Pump Application 1 ...
Страница 8: ...2 vacon 5 Safety ...
Страница 59: ...User Interfaces vacon 56 Service support find your nearest Vacon service center at www vacon com 4 ...
Страница 160: ...vacon 157 Parameters 6 ...
Страница 169: ...Fault vacon 166 Service support find your nearest Vacon service center at www vacon com 7 ...
Страница 170: ...7 vacon 167 Fault ...
Страница 171: ......