vacon • 24
STO and SS1 safety functions
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
Example 2: OPTBJ board with reset for Safe Torque Off or EN 60204-1 stop category 0.
The figure above presents a connection example of OPTBJ board for STO safety function with reset.
The switch S1 is connected with 4 wires to the OPTBJ board as shown above. The digital input 3
(DIN3), for example, is wired for the fault reset function. The reset function (not part of any safety
function) can be programmed to any of the available digital inputs.
The power supply to S1 may come from control board (connector pins 6 & 7 in Figure above) or it
may also be external, if earth fault and short circuit protected.
When the switch S1 is activated (contacts open), the drive will go to STO state and motor (if running)
will stop by coasting. The drive will indicate: "30 SafeTorqueOff".
To start the motor operation again, the following sequence is performed.
•
Release the switch S1 (contacts closed). The hardware is now enabled but the drive continues to dis-
play the fault "30 SafeTorqueOff".
•
Acknowledge the releasing of switch by edge sensitive reset function. The drive returns to the ready
state.
•
Giving a valid start command will start running the motor.
NOTE!
The Vacon 100 default application software uses edge-sensitive start as default start com-
mand, for preventing unexpected startup from STO state.
NOTE!
For EN 60204-1 emergency stop according to stop category 0, use the emergency stop but-
ton.
F1
1
2
3
4
5
6
L1
L2
MAIN CIRCUIT
L3
PE
PE
L1
L2
L3
U
V
W
PE
2
7
PE
PE
PE
W1
M1
M
3
~
U1
1
V1
W1
2
PE
R1
SPEED REFERENCE
S
CCW
CW
W12
1sh
1r
2sh
2p
2s
Basic I/O
1
+10Vref
1
2
AI1+
2
3
AI1
3
OPTBJ
SLOT E
1
STO1+
2
STO1
S1
11
12
W10
1r
2r
1b
2b
S6
START
13
14
4
AI2+
4
5
AI2
5
6
24Vout
6
7
GND
7
3
STO2+
4
STO2
21
22
S7
STOP
11
12
S8
RESET
13
14
8
DI1
8
9
DI2
9
10
DI3
10
11
CM
11
25
RO1 C
26
RO1 NO
28
TI1+
12
24Vout
12
13
GND
13
14
DI4
14
15
DI5
15
X23
OFF
29
TI1
16
DI6
16
17
CM
17
18
AO1+
18
19
AO/GND
19
30
+24Vin
20
PE
+24V
0V
Safe torque off
A
RS485
B
RS485
21
22
Short circuit and earth
fault protected supply
X10
Installed
3045A_UK
AO1
RS485
U
U
U
ON
OFF
I
I
I
AI2
AI1
ON
OFF
DGND
Содержание 100 INDUSTRIAL
Страница 1: ...vacon 100 ac drives optbj sto and atex option board safety manual...
Страница 2: ......
Страница 4: ...1 vacon 2 Approvals Tel 358 0 201 2121 Fax 358 0 201 212 205 1 APPROVALS...
Страница 5: ...Approvals vacon 3 24 hour support 358 0 201 212 575 Email vacon vacon com 1...
Страница 6: ...1 vacon 4 Approvals Tel 358 0 201 2121 Fax 358 0 201 212 205...
Страница 7: ...Approvals vacon 5 24 hour support 358 0 201 212 575 Email vacon vacon com 1...
Страница 8: ...1 vacon 6 Approvals Tel 358 0 201 2121 Fax 358 0 201 212 205...
Страница 9: ...Approvals vacon 7 24 hour support 358 0 201 212 575 Email vacon vacon com 1...