16
• vacon
Safe operating curves
Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
3
The safe operating curves for dU/dt filters 130B2841 - 43 are shown in figures 16 and
17. It is assumed that the default cable types have a capacitance of 55 - 60 nF/100 m.
The values should be scaled in accordance with the actual cable capacitance. In case
of multiple cables, the capacitance is the sum of the cable capacitances.
Figure 16. Safe operating curve for 130B2841 - 43 at 690 V mains supply.
Figure 17. Safe operating curve for 130B2841 - 43 at 500 V mains supply.