Table 10: M1.33 Multi-step speed
Index
Parameter
Min
Max
Unit
Default
ID
Description
1.33.1
Preset Frequency 1
P1.3
P1.4
Hz
10.0
105
1.33.2
Preset Frequency 2
P1.3
P1.4
Hz
15.0
106
1.33.3
Preset Frequency 3
P1.3
P1.4
Hz
20.0
126
1.33.4
Preset Frequency 4
P1.3
P1.4
Hz
25.0
127
1.33.5
Preset Frequency 5
P1.3
P1.4
Hz
30.0
128
1.33.6
Preset Frequency 6
P1.3
P1.4
Hz
40.0
129
1.33.7
Preset Frequency 7
P1.3
P1.4
Hz
50.0
130
1.33.8
Preset Frequency
Mode
0
1
0
128
0 = Binary Coded
1 = Number of inputs.
Preset frequency is
selected according to
how many of preset
speed digital inputs
are active.
1.33.9
External Fault
(Close)
DigIN
SlotA.3
405
CLOSED = OK
OPEN = External fault
1.33.10
Fault Reset (Close)
DigIN
Slot0.1
414
Resets all active faults
when CLOSED
1.4.4
PID CONTROL APPLICATION
You can use the PID control application with processes where you control the process
variable (for example pressure) through control of the speed of the motor.
In this application, the internal PID controller of the drive is configured for 1 setpoint and 1
feedback signal.
It is possible to use 2 control places. Make the selection of the control place A or B with DI6.
When control place A is active, the start/stop commands are given by DI1, and the PID
controller gives the frequency reference. When control place B is active, start/stop
commands are given by DI4, and AI1 gives the frequency reference.
It is possible to configure all the drive outputs freely in all the applications. There are 1
analogue output (Output Frequency) and 3 relay outputs (Run, Fault, Ready) available on the
basic I/O board.
QUICK STARTUP GUIDE
VACON · 33