5.9
GROUP 3.9: PROTECTIONS
Table 65: General protections settings
Index
Parameter
Min
Max
Unit
Default
ID
Description
P3.9.1.2
Response to External
Fault
0
3
2
701
0 = No action
1 = Alarm
2 = Fault (Stop accord-
ing to stop function)
3 = Fault (Stop by
coasting)
P3.9.1.3
Input Phase Fault
0
1
0
730
0 = 3-phase support
1 = 1-phase support
P3.9.1.4
Undervoltage Fault
0
1
0
727
0 = Fault stored in his-
tory
1 = Fault not stored in
history
P3.9.1.5
Response to Output
Phase Fault
0
3
2
702
P3.9.1.6
Response to Field-
bus Communication
Fault
0
5
3
733
0 = No action
1 = Alarm
2 = Alarm + preset fault
frequency (P3.9.1.13)
3 = Fault (Stop accord-
ing to stop function)
4 = Fault (Stop by
coasting)
P3.9.1.7
Slot Communication
Fault
0
3
2
734
P3.9.1.8
Thermistor Fault
0
3
0
732
P3.9.1.9
PID Soft Fill Fault
0
3
2
748
P3.9.1.10
Response to PID
Supervision Fault
0
3
2
749
P3.9.1.11
Response to External
PID Supervision
Fault
0
3
2
757
P3.9.1.12
Earth Fault
0
3
3
703
P3.9.1.13
Preset Alarm Fre-
quency
P3.3.1.1 P3.3.1.2
Hz
25.00
183
P3.9.1.14
Response to Safe
Torque Off (STO)
Fault
0
2
2
775
0 = No action
1 = Alarm
2 = Fault (Stop by
coasting)
VACON · 130