Parameters
vacon • 93
Local contacts: https://www.danfoss.com/en/contact-us/contacts-list/
7.1.2.3
Group 3.1.3: Limits
7.1.2.4
Group 3.1.4: Open loop
Table 61. Motor limit settings
Code
Parameter
Min
Max
Unit
Default
ID
Description
P3.1.3.1
Varies
Varies
A
Varies
107
Maximum motor current from AC
drive
P3.1.3.2
MotorTorqueLimit
0.0
300.0
%
300.0
1287
Maximum motoring side torque
limit
P3.1.3.3
GenerTorqueLimit
0.0
300.0
%
300.0
1288
Maximum generating side torque
limit
P3.1.3.4
MotorPowerLimit
0.0
300.0
%
300.0
1290
Maximum motoring side power
limit
P3.1.3.5
GenerPowerLimit
0.0
300.0
%
300.0
1289
Maximum generating side power
limit
Table 62. Open loop settings
Code
Parameter
Min
Max
Unit
Default
ID
Description
P3.1.4.1
0
2
0
108
Type of U/f curve between zero
frequency and the field weaken-
ing point.
0=Linear
1=Squared
2=Programmable
P3.1.4.2
Field WeakngPnt
8.00
Hz
Varies
602
The field weakening point is the
output frequency at which the
output voltage reaches the field
weakening point voltage
P3.1.4.3
10.00
200.00
%
100.00
603
Voltage at field weakening point
in % of motor nominal voltage
P3.1.4.4
U/f Mid Freq
0.00
Hz
Varies
604
Provided that the programmable
U/f curve has been selected (par.
P3.1.4.1), this parameter defines
the middle point frequency of the
curve.
P3.1.4.5
U/f Mid Voltg
0.0
100.0
%
100.0
605
Provided that the programmable
U/f curve has been selected (par.
P3.1.4.1), this parameter defines
the middle point voltage of the
curve.
P3.1.4.6
Zero Freq Voltg
0.00
40.00
%
Varies
606
This parameter defines the zero
frequency voltage of the U/f
curve. The default value varies
according to unit size.
P3.1.4.7
Flying Start Options
0
1
0
1590
Check box selection:
B0 = Search shaft frequency from
same direction as frequency ref-
erence.
B1 = Disable AC scanning
B4 = Use frequency reference for
initial guess
B5 = Disable DC pulses