Group 3.24: Dual Supply
Table 124. Common settings
Code
Parameter
Min
Max
Unit
Default
ID
Description
P3.24.1.1
AC Voltage
210
700
V
0
1974 Nominal voltage of AC grid.
V3.24.1.2
Nominal DC Voltage
0
1200
V
0
1990
Monitor of calculated value of
nominal DC voltage, when supply
is from AC grid.
P3.24.1.3
Dual Supply Mode
0
2
0
1971
0 = Always active
1 = Closed loop Irradiation
2 = Closed loop Sensorless
P3.24.1.4
1
100
V
30
1977
Offset added to M3.24.1.1, as DC
voltage threshold above which AC
can be switched Off.
P3.24.1.5
1
3600
s
60
1973
Delay to switch AC Off at stop, if it
happened with AC On condition.
Table 125. Mode 0 parameters
Code
Parameter
Min
Max
Unit
Default
ID
Description
P3.24.2.1
At Run
At Start
At Run
1972
Table 126. Mode 1 Irradiation parameters
Code
Parameter
Min
Max
Unit
Default
ID
Description
P3.24.3.1
Irradiation Signal
AI1
AI2
AI1
1980 Selection between AI1 and AI2.
P3.24.3.2
Max Irradiation
100
5000
W/m
2
1500
1981
Value of irradiation at maximum
signal.
P3.24.3.3
AC On Irradiation
0
1500
W/m
2
200
1984
Threshold for irradiation, below
which AC relay is switched On.
P3.24.3.4
AC Off Irrad. Offset
10
1500
W/m
2
200
1985
Value added to P3.24.3.3 to deter-
mine the threshold for switching
AC Off.
P3.24.3.5
Irrad. Stabiliz. Time
1
120
s
20
1986
Irradiation has to stay below/
above thresholds for this time, to
activate switching On/Off.
P3.24.3.6
Identification
No
Yes
No
1987
P3.24.3.7
20,00
50,00
Hz
30,00
1988