vacon • 132
Parameters
Local contacts: https://www.danfoss.com/en/contact-us/contacts-list/
7.1.15
Group 3.14: ExtPID Controller
7.1.15.1
Group 3.14.1: Basic settings
For more detailed information, see chapter 7.1.14.
Table 114. Sleep - no demand detected
Code
Parameter
Min
Max
Unit
Default
ID
Description
P3.13.10.1
Sleep No Demand
Detection Enable
0
1
0
1649
0 = No
1 = Yes
P3.13.10.2
SNDD Error Hysteresis
0
99999.9
P3.13.
1.4
0.5
1658
P3.13.10.3
SNDD Frequency Hys-
teresis
0.00
P3.3.1.2
Hz
3.00
1663
P3.13.10.4
SNDD Supervision
Time
0
600
s
120
1668
P3.13.10.5
SNDD Actual Add
0.00
P3.13.10.
2
P3.13.
1.4
0.5
1669
Table 115. Basic settings for external PID-controller
Code
Parameter
Min
Max
Unit
Default
ID
Description
P3.14.1.1
Enable ExtPID
0
1
0
1630
0 = Disabled
1 = Enabled
P3.14.1.2
Start signal
DigIN
Slot0.2
1049
FALSE = PID2 in stop mode
TRUE = PID2 regulating
This parameter will have no effect
if PID2 controller is not enabled in
the Basic menu for PID2
P3.14.1.3
Output in Stop
0.0
100.0
%
0.0
1100
The output value of the PID con-
troller in % of its maximum output
value while it is stopped from digi-
tal input
P3.14.1.4
Gain
0.00
1000.00
%
100.00
1631
P3.14.1.5
Integration Time
0.00
600.00
s
1.00
1632
P3.14.1.6
Derivation Time
0.00
100.00
s
0.00
1633
P3.14.1.7
ProcessUnitSel.
0
37
0
1635
P3.14.1.8
ProcessUnitMin
Varies
Varies
Varies
0
1664
P3.14.1.9
ProcessUnitMax
Varies
Varies
Varies
100
1665
P3.14.1.10
ProcessUnitDeci
0
4
2
1666
P3.14.1.11
Error inversion
0
1
0
1636
P3.14.1.12
Varies
Varies
Varies
0.0
1637
P3.14.1.13
0.00
320.00
s
0.00
1638