Parameters
vacon • 169
Local contacts: https://www.danfoss.com/en/contact-us/contacts-list/
7.2.16
Feedbacks
The PID controller output is locked if the actual value stays within the dead band area around the
reference for a predefined time. This function will prevent unnecessary movement and wear on ac-
tuators, e.g. valves.
Figure 62. Dead band
9097.emf
Dead band (ID1056)
Reference
Dead band delay (ID1057)
Output locked
Actual value