vacon • 102
Parameters
Local contacts: https://www.danfoss.com/en/contact-us/contacts-list/
7.1.6
Group 3.5: I/O Config
7.1.6.1
Default assignments of programmable inputs
Table 72 below presents the default assignments of programmable digital and analogue inputs in
VACON
®
100 X Solar Pump application.
7.1.6.2
Group 3.5.1: Digital inputs
Digital inputs are very flexible to use. Parameters are functions that are connected to the required
digital input terminal (see chapter 5). The digital inputs are represented as, for example,
DigIN Slot
A.2,
meaning the second input on slot A.
It is also possible to connect the digital inputs to time channels which are also represented as ter-
minals.
NOTE!
The statuses of digital inputs and the digital output can be monitored in the Multimonitoring
view.
Table 72. Default assignments of inputs
Input
Terminal(s)
Reference
Assigned function
Parameter code
DI1
8
A.1
Ctrl signal 1 A
DI2
9
A.2
Ctrl signal 2 A
DI3
10
A.3
External fault close
DI4
14
A.4
Preset frequency selection 0
P3.5.1.21
DI5
15
A.5
Preset frequency selection 1
P3.5.1.22
DI6
16
A.6
External fault close
AI1
2/3
A.1
AI1 signal selection
AI2
4/5
A.2
AI2 signal selection
Table 73. Digital input settings
Code
Parameter
Default
ID
Description
P3.5.1.1
Ctrl signal 1 A
DigIN SlotA.1
403
Ctrl signal 1 when control place is I/O A (FWD)
P3.5.1.2
Ctrl signal 2 A
DigIN SlotA.2
404
Ctrl signal 2 when control place is I/O A (REV)
P3.5.1.4
Ctrl signal 1 B
DigIN Slot0.1
423
Start signal 1 when control place is I/O B
P3.5.1.5
Ctrl signal 2 B
DigIN Slot0.1
424
Start signal 2 when control place is I/O B
P3.5.1.7
I/O B Ctrl Force
DigIN Slot0.1
425
TRUE = Force the control place to I/O B
P3.5.1.8
I/O B Ref Force
DigIN Slot0.1
343
TRUE = Used frequency reference is specified by I/O
reference B parameter (P3.3.1.6).
P3.5.1.9
Fieldbus Ctrl Force
DigIN Slot0.1
411
Force control to fieldbus
P3.5.1.10
Keypad Ctrl Force
DigIN Slot0.1
410
Force control to keypad
P3.5.1.11
Ext Fault Close
DigIN SlotA.3
405
FALSE = OK
TRUE = External fault
P3.5.1.12
Ext Fault Open
DigIN Slot0.2
406
FALSE = External fault
TRUE = OK
P3.5.1.13
Fault Reset Close
DigIN SlotA.6
414
Resets all active faults when TRUE
P3.5.1.14
Fault Reset Open
DigIN Slot0.1
213
Resets all active faults when FALSE
P3.5.1.15
DigIN Slot0.2
407
Must be on to set drive in Ready state