I
NSTALLATION
VACON
•
11
24-hour support (0)201 212 575 • Email: [email protected]
3
3.1.2 Cooling
Enough free space shall be left above and below the frequency converter to ensure
sufficient air circulation and cooling. You will find the required dimensions for free
space in the table below.
If several units are mounted above each other the required free space equals C + D
(see Installation space). Moreover, the outlet air used for cooling by the lower unit
must be directed away from the air intake of the upper unit.
The amount of cooling air required is indicated below. Also make sure that the tem-
perature of the cooling air does not exceed the maximum ambient temperature of
the converter.
*. Min clearance A and B for drives for
MI1 ~ MI3 can be 0 mm if the ambient
temperature is below 40 degrees.
Figure 3.5: Installation space
A = clearance around the freq. converter (see also B)
B = distance from one frequency converter to another or distance to
cabinet wall
C = free space above the frequency converter
D = free space underneath the frequency converter
NOTE!
See the mounting dimensions on the back of the drive.
Leave
free space
for cooling above
(100 mm)
, below
(50 mm)
, and on the sides
(20 mm)
of Vacon 10! For MI1 - MI3, side-to-side installation allowed only if the am-
bient temperature is below 40 °C
.
Min clearance (mm)
Frame
A*
B*
C
D
MI1
20
20
100
50
MI2
20
20
100
50
MI3
20
20
100
50
Table 3.5: Min. clearances around AC drive
Frame
Cooling air required (m³/h)
MI1
10
MI2
10
MI3
30
Table 3.6: Required cooling air
B
C
B
A
D
A
Содержание 10 PFC
Страница 1: ...vacon 10 ac drives vacon 10 pfc user manual...
Страница 2: ......
Страница 15: ...INSTALLATION VACON 13 24 hour support 0 201 212 575 Email vacon vacon com 3 MI1 MI3 3P 230 V POWER LOSS...
Страница 16: ...14 VACON INSTALLATION Tel 358 0 201 2121 Fax 358 0 201 212 205 3...
Страница 17: ...INSTALLATION VACON 15 24 hour support 0 201 212 575 Email vacon vacon com 3 MI1 MI3 1P 230 V POWER LOSS...
Страница 18: ...16 VACON INSTALLATION Tel 358 0 201 2121 Fax 358 0 201 212 205 3...
Страница 25: ...INSTALLATION VACON 23 24 hour support 0 201 212 575 Email vacon vacon com 3 Figure 3 14 MI3 screws...
Страница 81: ......