FOR PLUGGABLE EQUIPMENT, the socket-outlet shall be installed near the equipment 

and shall be easily accessible. 

l

 

CAUTION: The unit is heavy. Lifting the unit requires a minimum of two people. 

 

7.4 Operation 

l

 

Do not disconnect the mains cable on the UPS system or the building wiring outlet 
(shockproof socket outlet) during operations since this would cancel the protective 
earthing of the UPS system and of all connected loads.   

l

 

The UPS system features its own, internal current source (batteries). The UPS output 
sockets, or output terminals block may be electrically live even if the UPS system is 
not connected to the building wiring outlet.   

l

 

To fully disconnect the UPS system, first press the OFF/Enter button to disconnect the 
mains.   

l

 

Prevent fluids and other foreign objects from entering the UPS.   

l

 

The EPO and USB circuits are an IEC 60950-1 safety extra low voltage (SELV) circuit. 
This  circuit  must  be  separated  from  any  hazardous  voltage  circuits  by  reinforced 
insulation. 

 

7.5 Maintenance, service, and faults 

l

 

The UPS system operates with hazardous voltages. Repairs may be carried out only 
by qualified maintenance personnel.   

l

 

Caution - 

risk of electric shock. Even after the unit is disconnected from the mains 

(building wiring outlet), components inside the UPS system are still connected to the 
battery and electrically live and dangerous.   

l

 

Before carrying out any kind of service and/or maintenance, disconnect the batteries 
and verify that no current is present, and no hazardous voltage exists in the terminals 
of high capability capacitor such as BUS-capacitors.   

l

 

To avoid electrical shock, turn off the unit and unplug it form the AC power source 
before servicing the battery. 

l

 

Only persons are adequately familiar with batteries and with the required 
precautionary measures may replace batteries and supervise operations.   

l

 

Caution -

 risk of electric shock. The battery circuit is not isolated from the input 

voltage. Hazardous voltages may occur between the battery terminals and the 
ground. Before touching, verify that no voltage is present!   

l

 

Caution - 

Do not dispose of batteries in a fire. The batteries may explode.   

l

 

Caution -

 Do not open or mutilate batteries. Released electrolyte is harmful to the 

skin and eyes. It may be toxic. 

l

 

A battery can may cause a risk of electrical shock and high short-circuit current. The 

following precautions should be observed when working on batteries: 

a)

 

Remove watches, rings, or other metal objects 

b)

 

Use tools with insulated handles. 

c)

 

Wear rubber gloves and boots. 

d)

 

Do not contact batteries with tools or other metal parts. 

e)

 

Disconnect charging source prior to connecting or disconnecting battery terminals. 

f)

 

Determine if battery is inadvertently grounded. If inadvertently grounded, remove 
source from ground. Contact with any part of a grounded battery can result in 
electrical shock.   

Содержание UPS2URM3000DC-NC-1N

Страница 1: ...UPS2URM3000DC NC 1N User Guide...

Страница 2: ...Modem surge protection 5 USB communication port 6 RS 232 communication port 7 SNMP intelligent port 8 Emergency power off function connector EPO 9 External battery connection not supported 1 1 Operat...

Страница 3: ...t connecting battery wires Before installation of the UPS please follow the steps below to re connect the battery wires Rack Mount Installation Caution DO NOT use the mounting brackets to lift the uni...

Страница 4: ...mm in the rear of the UPS Operate at or below a maximum altitude of 3000m for normal operation at full load 2 UPS input connection Plug the UPS into a two pole three wire grounded receptacle only Avoi...

Страница 5: ...ing software installed you can schedule UPS shutdown start up and monitor UPS status through PC The UPS is equipped with an SNMP Network card When installing either SNMP for advanced communications an...

Страница 6: ...power to change the batteries press the OFF button on the front panel for two seconds to power off the UPS and switch off utility power where the UPS is connected DO NOT DISCONNECT the batteries while...

Страница 7: ...rior to connecting or disconnecting battery terminals Remove battery grounds during installation and maintenance to reduce the risk of shock Remove the connection from ground if any part of the batter...

Страница 8: ...onfirm selection in UPS setting mode Select Button Switch LCD message Press this button to change the LCD message for input voltage input frequency input current battery voltage battery current batter...

Страница 9: ...oad current and load percent k kilo W watt V voltage A ampere percent centigrade degree Hz frequency Load information Indicates the load level by 0 24 25 49 50 74 and 75 100 Indicates overload Program...

Страница 10: ...lay content Meaning ENA Enable DIS Disable ESC Escape HLS High loss LLS Low loss AO Active open AC Active close EAT Estimated autonomy time RAT Running autonomy time SD Shutdown OK OK ON ON BL Battery...

Страница 11: ...125VAC 127 presents output voltage is 127VAC 127VAC is not applicable in US region l 02 Frequency Converter enable disable Interface Setting Parameter 2 Enable or disable converter mode CF ENA convert...

Страница 12: ...eptable high voltage point and acceptable low voltage point for Bypass mode by pressing the Down key or Up key HLS Bypass high voltage point For 100 110 115 120 125 127VAC models 120 140 Set the high...

Страница 13: ...or programmable outlets which connect to non critical devices on battery mode Default 999 l 11 Autonomy limitation setting Interface Setting Parameter 2 Set the backup time on battery mode for general...

Страница 14: ...o 2 40V cell Default 2 36V cell l 15 Charger float voltage setting Interface Setting Parameter 2 Set the charger float voltage 2 20 2 33 Set the charger float voltage from 2 20 V cell to 2 33V cell De...

Страница 15: ...he UPS will bypass voltage to output for energy saving The UPS also charges the battery in ECO mode Frequency Converter mode When input frequency is within 40 Hz to 70 Hz the UPS can be set to a const...

Страница 16: ...Over input current Sounds 2 beeps every 10 seconds Battery is not connected Sounds every 2 seconds Over Charge Sounds every 2 seconds Site wiring fault Sounds every 2 seconds EPO enable Sounds every 2...

Страница 17: ...t v7 world com Fault code 28 is displayed on the LCD and the alarm is continuously sounding Battery voltage is too low or there is a charger fault Contact your reseller or techsupport v7 world com The...

Страница 18: ...ing of a connected external battery pack for short circuited Fault code 45 is displayed on the on the LCD display and the alarm is continuously sounding No charger output and battery voltage is less t...

Страница 19: ...aveform Batt Mode Pure Sinewave EFFICIENCY AC Mode 91 full charged battery ECO Mode 96 full charged battery Battery Mode 90 BATTERY Battery Type 12V 9AH Number 6 Recharge Time 3 hours recover to 95 ca...

Страница 20: ...or near heat sources l Avoid blocking ventilation holes in the UPS enclosure 7 3 Installation l Do not connect appliances or devices which can overload the UPS system e g laser printers l Route cables...

Страница 21: ...electrically live and dangerous l Before carrying out any kind of service and or maintenance disconnect the batteries and verify that no current is present and no hazardous voltage exists in the termi...

Отзывы: