Troubleshooting
Problem
Possible Cause
Solutions
Nothing is displayed on
the panel
The UPS is not on
Press the power switch again to turn on
the UPS
Battery voltage is too low Charge the battery at least 6 hours
Battery fault
Replace the battery
The UPS always on
battery mode
Power cord is loose
Re-plug the power cord
The UPS continuously
beeps
Please check the fault
code for details
Check the fault code table for details
Backup time too short
Battery voltage is too low Charge the battery at least 6 hours
Overload
Remove some unnecessary loads. Before
reconnecting equipment, please verify
that the load matches the UPS capability
in the specifications of your UPS
Battery defect
Replace the battery
Fault Code Table
Fault Condition
LCD
Solutions
Output short circuited
Disconnect short-circuited loads and
restart the UPS again
Inverter/Output failure
Call for service immediately
Overcharge
1. Turn off the unit and wait for cooling.
2. Or remove excessive loads and wait
for cooling.
Note
: If fault alarm occurs, please call for service immediately.
Specifications
Model
1500
CAPACITY
1500VA/900W
Input Voltage
230 VAC
Input Voltage Range
170-270 VAC
Output Voltage Regulation
± 5 % (Bat. mode)
Transfer Time
Typical 6 ms, max. 10 ms
Waveform
Simulated Sine Wave
Battery Type & No
12V/9Ah x 2
Charging Time
6-8 hours recover to 90% capacity
Dimension (DxWxH)
16” x 4” x 11”
Net Weight
26lbs (11.79 kg)
Humidity
0-90% RH @ 0-40°C non-condensing
Noise Level
Less than 45dB @ 1 meter (3 ft.)