![V-TAC VT-6605105 Скачать руководство пользователя страница 13](http://html1.mh-extra.com/html/v-tac/vt-6605105/vt-6605105_instruction-manual_3105372013.webp)
INSTALLATION PLACE
Select installation place based on the following considerations:
(1) The height of the installation position should ensure that the line of sight is at the same
level as the LCD for viewing the parameters of inverter conveniently.
(2) Select a well ventilated place sheltered from direct sun radiation and rain.
(3) Allow sufficient space around the inverter to enable easy installation and removal from
the mounting surface and air convection. (See Figure 8).
(4) The ambient temperature of installation should be -25°C~60°C
(5) The installation site should be away from electronic devices which can generate strong
electromagnetic interference.
(6) The inverter needs to be installed on a firm and sturdy surface, such as wall and metal
bracket and so on.
(7) The installation surface should be perpendicular to the horizontal line. (See Figure 9)
(8) The installation should ensure that the inverter is reliably grounded, and the material of
grounded metal conductor should be consistent with the metal material reserved for the
grounding of the inverter.
BEFORE INSTALLATION
Installation tools
Table of detailed delivery list of single-phase inverter
N O
N A M E
Q UA N T IT Y
1
3KW-2M / 5KW-2M
1
2
Installatio n bracket
1
3
Operatio n manual
1
4
B o lt M 5*20
2
5
Expansio n bo lts M 6*60
3KW-2M / 5KW-2M
6
Co mmunicatio n co nnecto r
1
7
DC co nnecto r
3KW-2M / 5KW-2M:2 pairs
8
A C co nnecto r
1
Table of tools list
N O
IN S T A LLA T IO N T O O LS
IN S T R UC T IO N
1
M arking pen
M ark the installatio n ho le
2
Electro drill
Drill in the bracket o r wall
3
Hammer
Hammer o n the expansio n bo lts
4
M o nkey wrench
Fix the installatio n bracket
5
A llen driver
Fasten the screws, remo ve and install A C wiring bo x
6
Straight screwdriver
Fo r A C wiring
7
M egger
M easuring insulatio n perfo rmance and impedance
8
M ultimeter
Check the circuit and A C and DC vo ltage
9
Electric iro n
Weld co mmunicatio ns cable
10
Wire crimper
Crimp DC terminals