WARNING:
• This product must be disconnected from the circuit if subjected to any high voltage or
insulation resistance testing. Irreparable damage will occur if this instruction is not
followed
• Recommended routine test procedure in accordance with BS5266
• Daily check – check that the status GREEN LED indicator is illuminated
• Monthly functional test – simulate a mains supply failure for approx. 30 secs by
operation of key switch or switching off a circuit breaker. Ensure normal supply is
restored after test and the indicator status LED is illuminated
• Twice yearly conduct a one hour duration test - simulate a mains supply failure for one
hour continuous test by operation of key switch or switching off circuit breaker. Ensure
normal supply is restored after test and the indicator status LED is illuminated
• Annual full three hour duration test - conduct a three hour continuous duration test.
Simulate a mains supply failure for three hour continuous test by operation of key switch
or switching off circuit breaker. Ensure normal supply is restored after test and the
indicator status LED is illuminated
• If the luminaire fails any of the above tests, please contact a qualified electrician.