VG-6647 Digital Multi-sense Detector 

Installation and Operation Manual V1.05

 

3.Address range should be within 0

255. The address is unique in a loop.

Sensor setting 

VG-6647  has  two  temperature  response  modes  and  one  smoke  sensitivity  mode.  The  temperature  modes  are 

A1R  &A2  and  the  smoke  sensitivity  is  set  at  one  default  setting,  which  is  equivalent  to  our  VG-6627  Smoke 

detector Mode 2: 0.126 dB/m. The details of temperature modes please see the following table. 

Temp. 

Mode 

Class 

Application Temperature 

Static Response Temperature 

Typical 

Maximum 

Min 

Max 

A1R 

25 

50 

54 

65 

A2 

25 

50 

54 

70 

Mode 1

 is Factory Setting.

The letter 

“R” suffix means that the heat responseclass incorporates a rate-of-rise characteristic. It will give

rapid response even when high rates of rise of air temperature starting at air temperaturessubstantially

below the typical application temperature.

The sensor response mode of VG-6647 can be set by Control Panel, please refer to the corresponding

manual for details.

Testing 

Warning

Power is switched off before all devices are installed completely. 

The detector must be tested after installation or regular maintenance. 

Registration:

The  fire  alarm  control  panel  will  registers  the  detector  on  line  to  check  if  the  address  of  the

detectors mounted is the same address as that registered in the control panel.

Firecondition:

 After registration, make detector under fire conditions by using hot air generator and/or

Smoke generatorto test whether the detector alarms normally and control panel displays its registered

address.

Reset

After testing, reset the detector through control panel.

Fault Finding 

Detector  Fault  on 
Control Panel 

Check wiring of Common base, no water no short-circuits and open circuit. 

Check the connection between detector and common base. 

Nuisance alarm 

The detector alarm frequently  but there is no Fire and other unusual,  then check whether 
the chamber in the detector is too dirty and needs to be cleaned 

Otherwise, the circuit may be broken. 

Address Fault 

Address is set incorrectly, Reset by VG-6537 Digital Programmer. 