NivoRadar
®
Continuous level measurement
Series NR 4100
Technical information / Instruction manual
Diagnostics and servicing
page 37
Out of specification:
The measured value is unreliable because an instrument specifica-
tion was exceeded (e.g. electronics temperature).
This status message is inactive by default.
Maintenance required:
Due to external influences, the instrument function is limited. The
measurement is affected, but the measured value is still valid. Plan
in maintenance for the instrument because a failure is expected in
the near future (e.g. due to buildup).
This status message is inactive by default.
Code
Text message
Cause
Rectification
DevSpec
State in CMD 48
F013
no measured value
available
No measured value in the switch-
on phase or during operation
Check or correct installation and/
or parameter settings
Clean the antenna system
Byte 5, Bit 0 of
Byte 0 … 5
F017
Adjustment span
too small
Adjustment not within specifi-
cation
Change adjustment according
to the limit values (difference be-
tween min. and max. ≥ 10 mm)
Byte 5, Bit 1 of
Byte 0 … 5
F025
Error in the lineari-
zation table
Index markers are not continu-
ously rising, for example illogical
value pairs
Check linearization table
Delete table/Create new
Byte 5, Bit 2 of
Byte 0 … 5
F036
No operable soft-
ware
Checksum error if software up-
date failed or aborted
Repeat software update
Send instrument for repair
Byte 5, Bit 3 of
Byte 0 … 5
F040
Error in the elec-
tronics
Limit value exceeded in signal
processing
Hardware error
Restart instrument
Send instrument for repair
Byte 5, Byte 5,
Bit 4 of Byte 0 … 5
F080
General software
error
General software error
Restart instrument
Byte 5, Byte 5,
Bit 5 of Byte 0 … 5
F105
Determine meas-
ured value
The instrument is still in the
switch-on phase, the measured
value could not yet be deter-
mined
Wait for the end of the switch-
on phase
Duration up to 3 minutes de-
pending on the measurement
environment and parameter set-
tings
Byte 5, Byte 5,
Bit 6 of Byte 0 … 5
F260
Error in the cali-
bration
Checksum error in the calibra-
tion values
Error in the EEPROM
Send instrument for repair
Byte 4, Bit 0 of
Byte 0 … 5
F261
Error in the instru-
ment settings
Error during setup
False signal suppression faulty
Error when carrying out a reset
Repeat setup
Carry out a reset
Byte 4, Bit 1 of
Byte 0 … 5
Failure