13 - HEAD LOSS / FLOW
13.1 - Application guideline
For selecting the right automatic filter it is important to take a number of variables into account.
The origin of the water to be used, the degree of contamination and the application for the filtered water.
A pre-filter can sometimes be necessary. For any additional questions contact your supplier.
All our recommendations are without obligation, and we cannot be held liable for any adverse consequences
resulting from these recommendations.
Sizes 10", 14", 16", 18" and 20" are upon request.
��
See chapter 13.2 The assessment and use of the application guideline
Maximum flow in m3/h
Micron
filter element water quality
10*
25*
50*
80
100
130
200
≥ 300
2”-2500 cm²
good
10
25
25
25
25
25
25
25
fair
-
17
25
25
25
25
25
25
contaminated
-
15
20
25
25
25
25
25
3”-2500 cm²
good
10
25
40
40
40
40
40
40
fair
-
17
25
40
40
40
40
40
contaminated
-
15
20
33
40
40
40
40
4”-2500 cm²
good
10
25
42
58
75
80
80
80
fair
-
17
25
42
50
59
75
80
contaminated
-
15
20
33
42
50
68
75
4”-4000 cm²
good
16
40
67
80
80
80
80
80
fair
-
27
40
67
80
80
80
80
contaminated
-
21
32
53
67
80
80
80
6”-4000 cm²
good
16
40
67
94
120
133
150
150
fair
-
27
40
67
80
94
134
134
contaminated
-
21
32
53
67
80
120
120
6”-6000 cm²
good
24
60
100
140
150
150
150
150
fair
-
40
60
100
120
141
150
150
contaminated
-
32
50
80
100
120
150
150
8”-6000 cm²
good
24
60
100
140
180
200
240
240
fair
-
40
60
100
120
141
200
200
contaminated
-
32
50
80
100
120
160
180
8”-8000 cm²
good
32
80
133
160
250
270
300
300
fair
-
53
80
133
160
188
250
300
contaminated
-
43
64
106
133
160
220
250
12”-8000 cm²
good
32
80
133
185
250
270
500
600
fair
-
53
80
133
160
188
268
270
contaminated
-
43
64
106
133
160
240
250