Installation Procedure 

 
The UV disinfection system should be the last step of your water 
treatment system.  Choose a location for installation with a close 
electrical outlet.  Note the direction of water flow in the supply line. 
Refer to the plumbing diagram and check that you have all necessary 
fittings for installation.  

Note

: A minimum of 36” clearance at lamp 

cord end of the chamber will allow most maintenance procedures to 
be accomplished without removing the disinfection chamber from its 
mounting bracket. 
 

n

Shut off the main water supply valve. 

 

o

Mount the unit to the wall using the mounting brackets provided. 

Mount ballast on the bracket beside the chamber. 
 

p

Install new plumbing as per diagram. 

Note

: When installing the 5 

micron pre-filter, make sure the flow arrows on them point in the same 
direction as the water flow. 

WARNING: if soldering, do not allow 

heat near plastic threads or fittings.

 

 

q

Carefully insert the quartz sleeve into the disinfection chamber and 

place “O” rings over both sleeve ends. Adjust the position of the 
sleeve and “O” rings so that equal amount of sleeve is protruding from 
both ends of the disinfection chamber.  
 

r

Install the glandnuts and tighten. The bottom glandnut is equipped 

with a black plastic insert to prevent leakage of UV light. 
 

s

Place the lamp spring and the lamp into the quartz sleeve, and 

holding the top of the lamp, attach lamp to the lamp connector. Push 
down the lamp connector snugly into the glandnut. 
 

t

Remove the nut from the ground stud at the top of the unit. Next 

place the ground wire (green wire with yellow stripe) over the stud and 
re-install nut and tighten. 

FAILURE TO GROUND CHAMBER MAY 

RESULT IN ERRATIC UV SENSOR BEHAVIOUR 

 

u

Install UV detector probe.  The probe must be tightened down 

completely to insure accurate calibration. If the probe cannot be hand 
tightened, use locking pliers with minimum pressure required to grip 
the probe body securely to finish installation. Connect UV detector 
probe plug into port labeled UV sensor on the UV power source. 

Caution – 

Do not over tighten. 

 

v

Open valves on either side of the disinfection chamber.  Check for 

leaks. Open supply valve slowly and bleed air from system. 
 

w

Connect UV power source to AC line. UV power source audio 

alarm will sound three times before igniting the lamp. 
 
Your UV Dynamics disinfection system is now ready for service. 
Before service begins, all household plumbing lines should be 
chemically disinfected. 
 
 
 

 

DISINFECTION PROCEDURE 

 

 

 

THE FOLLOWING DISINFECTION PROCEDURE IS GENERALLY 
ACCEPTED AS BEING SUITABLE FOR THE DISINFECTION OF 
PLUMBING SYSTEMS KNOWN TO BE CONTAMINATED.  
 
IF YOU ARE UNCERTAIN ABOUT THE EFICCACY OF THIS 
PROCEDURE YOU ARE ADVISED TO CONTACT THE LOCAL 
HEALTH AUTHORITY RESPONSIBLE FOR WATER SAFETY

  

As the UV disinfection process takes place only in the UV disinfection 
chamber and the process provides no residual disinfection capability, 

therefore it is necessary to chemically disinfect the entire 
plumbing system before using water treated by the UV system. 

 

n

The disinfection of the plumbing system is most readily 

accomplished by removing the 5 micron sediment filter cartridge

 

and 

adding 250ml - 500ml  (1 –2 cups) of standard 5.25% concentration 
un-scented chlorine bleach to the empty filter housing and  
re-installing. 

o

Verify that the UV disinfection unit is connected to the AC supply 

voltage and operating properly. 
 

p

Operate 

all faucets, fixtures and appliances

 until you clearly 

smell chlorine and shut off. 

This includes shower heads, outside taps, 

dishwashers, laundry equipment and any appliance connected to the 
plumbing system.

 

       

q

Leave the bleach solution for 30 minutes. 

 

r

Re-install the sediment filter cartridge and thoroughly flush the 

system at all fixtures and appliances connected to the system. 
 

Note:

 The introduction of a chlorine disinfection solution to a hot water 

heater that has been used with untreated hard water or water with 
excessive iron, manganese or other organic contaminants may lead to 
oxidization of these materials. If you feel that these conditions may 
apply to your installation, a thorough flushing of the hot water tank 
should be undertaken to eliminate the oxidized material from the 
system. 
    

UV POWER SOURCE FEATURES

 

 

 

The micro-processor controlled UV power source supplied with the 

UVD1000S has both audio and visual alarm indicators to validate 
lamp operation and an integral annual lamp change reminder timer.  
A two digit seven segment display is provided to display relative UV 
level, lamp life remaining when timer button is pressed and various 
error codes to aid in system diagnostics. If the relative UV level falls 
below 50%, the unit goes into the low UV alarm mode and the 
solenoid valve, if installed, will be de-activated. 
 

UV power source initialization sequence:

 When AC power is 

applied to the UV power source, the lamp is ignited as indicated by 
the green lamp-on LED after which a self test of the annual lamp 
change reminder timer LED and alarm buzzer consisting of three 
buzzer beeps and three red timer LED flashes. The two digit display 
indicates the relative UV level. If a solenoid is connected to the UV 
power source, it will activate when the UV level reaches 50%.  

 
Normal Operation:

 During normal operation, the green lamp-on LED 

is illuminated and the two digit display indicates the relative UV 
intensity. 

 
Lamp failure: 

When the UV power source detects a lamp failure or 

enters the auto shut down mode due to abnormal operating 
conditions, the alarm buzzer sounds and the green lamp-on LED is 
extinguished. If connected, the solenoid valve will terminate the water 
flow. 

 
Lamp timer operation: 

The annual lamp change reminder timer will 

run for approximately one full year. At the end of the one year period 
the lamp change reminder timer will flash and the buzzer will sound. 
The flashing LED indicates that the timer function is in the 28 day 
grace period. Pushing the timer button during this grace period will 
silence the buzzer for a seven day period but the LED will continue to 
flash. The buzzer reset can be activated a maximum of four times 
during the 28 day grace period. Under no circumstance does the 
grace period exceed 28 days. At the expiry of the 28 day grace period 
the UV power source indicates the lamp change alarm mode by 
illuminating the red timer LED continuously and displaying the error 
code 

E5 

and sounding the buzzer. 

Note: The UV lamp is not shut 

down in this alarm mode and the solenoid valve drive is not disabled.

  

 
 
 
 
 
 
 
 
 
 

 