AC-PRO Retrofit ............................................................ DS206 TO 850
Page 13
10.0
Final Test
Perform a final electrical test of the breaker as in Section 2.
In accordance with ANSI C37.50-1989, A.3.7, each retrofitted
breaker must be tested.
Utility Relay Company recommends the following tests at a
minimum:
a)
Dielectric
b)
Primary injection pick-up and trip.
c)
Resistance measurement of main contacts and
conductors.
d)
Trip free operation of actuator.
Содержание AC-PRO Retrofit Kit
Страница 2: ...Courtesy of NationalSwitchgear com ...
Страница 23: ...Courtesy of NationalSwitchgear com ...
Страница 24: ...Courtesy of NationalSwitchgear com ...
Страница 25: ...Courtesy of NationalSwitchgear com ...
Страница 26: ...Courtesy of NationalSwitchgear com ...
Страница 27: ...Courtesy of NationalSwitchgear com ...
Страница 28: ...Courtesy of NationalSwitchgear com ...
Страница 29: ...Courtesy of NationalSwitchgear com ...
Страница 30: ...Courtesy of NationalSwitchgear com ...
Страница 31: ...Courtesy of NationalSwitchgear com ...
Страница 32: ...Courtesy of NationalSwitchgear com ...
Страница 33: ...Courtesy of NationalSwitchgear com ...
Страница 34: ...Courtesy of NationalSwitchgear com ...
Страница 35: ...Courtesy of NationalSwitchgear com ...
Страница 36: ...Courtesy of NationalSwitchgear com ...
Страница 37: ...Courtesy of NationalSwitchgear com ...
Страница 38: ...Courtesy of NationalSwitchgear com ...
Страница 39: ...Courtesy of NationalSwitchgear com ...
Страница 40: ...Courtesy of NationalSwitchgear com ...
Страница 41: ...Courtesy of NationalSwitchgear com ...
Страница 42: ...Courtesy of NationalSwitchgear com ...
Страница 43: ...Courtesy of NationalSwitchgear com ...
Страница 44: ...Courtesy of NationalSwitchgear com ...