82
Is this a new boiler on first startup?
NO
YES
LP Conversion Kit installed?
NO
YES
Connect All Wires And
Assure Secure Fit
Open the gas shutoff
valve
E14
- Burner Start Up
Failures
LP installation?
NO
YES
Troubleshooting Chart 5
Check all wires including
igniter and gas valve are
connected and tight
NO
YES
Check Gas Line For Obstructions
Install
Conversion Kit
Is the gas shutoff valve closed?
NO
YES
13 - TROUBLE SHOOTING
Are ground wires attached and boiler
properly grounded?
NO
YES
Provide Proper
Ground
Has all air been purged
from gas line?
NO
YES
Purge all air
from gas line
Check gas inlet pressure at least
equals rating plate requirements.
NO
YES
Press RESET for two (2) seconds and retry.
Is there a strong, consistent spark?
NO
YES
Remove igniter and inspect. Is
there contamination?
NO
YES
Clean Or Replace Igniter
Does the boiler ignite?
NO
YES
Restart the boiler and place into high fire
chimney sweep. Go to display and check
flame current. Is there at least 3 mA?
NO
YES
Hold the igniter and retry
ignition. Is there a spark?
NO
YES
Check Venting For Obstruction And
Or Wind Effects
Replace Spark
Generator
Remove burner and inspect. Any
sign of damage to burner surface?
NO
YES
Check interior of heat exchanger for
debris or other signs of blockage
NO
YES
Replace Burner
Replace Gas Valve
Clean Heat Exchanger
P/N 240011654, Rev. C [06/08/2017]