26
P/N 240009735, Rev. G [09/30/2016]
TABLE 5 - CARLIN EZ-1/2 SETTINGS
BOILER
MODEL
BURNER
MODEL
FIRING
RATE
NOZZLE
MFR.
NOZZLE
TYPE
PUMP
PRESSURE
[PSI]
HEAD
BAR
AIR BAND
SETTING
AIR
SHUTTER
3085
EZ-1HP
0�85
DELAVAN
0�75 x 70 B
130
0�75
45%
BLANK
3100
EZ-1HP
1�00
DELAVAN
0�85 x 70 B
140
0.85/1.00
55%
BLANK
4100
EZ-1HP
1�00
DELAVAN
0�85 x 70 B
140
0.85/1.00
52%
BLANK
4125
EZ-1HP
1�25
DELAVAN
1�00 x 70 B
155
0.85/1.00
70%
BLANK
4145
EZ-1HP
1�45
DELAVAN
1�20 x 70 B
145
1.10/1.25
78%
BLANK
5160
EZ-2HP
1�60
DELAVAN
1�35 x 70 B
140
0.85/1.00
20%
3 SLOT
5185
EZ-2HP
1�85
DELAVAN
1�50 x 70 B
155
1�50
30%
3 SLOT
6175
EZ-2HP
1�75
DELAVAN
1�50 x 60 B
140
1�50
35%
3 SLOT
6210
EZ-2HP
2�10
DANFOSS 1�75 x 70 AS
145
1.65/1.75
65%
OPEN
15 - BURNER SETTINGS
Above settings are preliminary settings only� Final adjustments must be made using combustion test instruments
as previously outlined in the Operating Instructions