![UTICA BOILERS OLSSV-050 Скачать руководство пользователя страница 57](http://html1.mh-extra.com/html/utica-boilers/olssv-050/olssv-050_installation-operation-and-maintenance-manual_1065181057.webp)
57
13 - TROUBLE SHOOTING
YES
Remo
ve all liquid
from connector
.
Check for leaks. Repair all leaks.
Replace Control Module
Replace R
eturn W
ater
Sensor
Is correct harness connected to return
sensor (2 Brown Wires)?
YES
NO
Correct wiring
Unplug molex connector on return sensor
. Is there moisture or liquid on
metal pins? Liquid might be w
ater or
antifreez
e solution.
NO
Is Primary Pump
properly oriented?
YES
NO
Disconnect harness from
Return W
ater Sensor
. Measure
resistance using digital ohm meter
. Is resistance between
950 to 33,000 ohms?
Install Primary Pump in proper
orientation
YES
NO
Replace
Control
Module
Verify
order of
pins
on
J2.
Pin
order
should
be:
empty,
black (or
red),
white,
green.
Measure volts
on
pins of
black
wire a
nd
white wire.
Is
wiring/pins in
right order?
D
oes black/wire have 120
VAC? D
oes
white wire/pin have
0
VAC?
P/N# 2400010616, Rev. F [10/26/2015]
Содержание OLSSV-050
Страница 50: ...50 13 TROUBLE SHOOTING P N 2400010616 Rev F 10 26 2015 ...
Страница 52: ...52 13 TROUBLE SHOOTING P N 2400010616 Rev F 10 26 2015 ...
Страница 64: ...64 14 1 Connection Diagram 050 075 100 MBH 14 WIRING DIAGRAM P N 2400010616 Rev F 10 26 2015 ...
Страница 65: ...65 14 2 Schematic Diagram of Ladder Form 050 075 100 MBH 14 WIRING DIAGRAM P N 2400010616 Rev F 10 26 2015 ...
Страница 66: ...66 14 3 Connection Diagram 150 200 MBH 14 WIRING DIAGRAM P N 2400010616 Rev F 10 26 2015 ...
Страница 67: ...67 14 4 Schematic Diagram of Ladder Form 150 200 MBH 14 WIRING DIAGRAM P N 2400010616 Rev F 10 26 2015 ...