21
14 - OPERATING YOUR BOILER
AUTOMATIC GAS VALVE
Automatic Gas Valve opens or closes according to
heat requirements of thermostat and temperature
limit control. It closes if pilot goes out. Each
individual control must be operating correctly before
any gas can pass to burners. Any one control can
hold gas supply from burner regardless of demand of
any other control.
SAFETY PILOT
Safety Pilot prevents
fl
ow of gas to burner if pilot
goes out, or will not ignite.
GAS VALVE SAFETY SHUTDOWN TEST
Ignition system safety shutoff device must be tested
after placing boiler in operation.
For boilers equipped with continuous pilot, with
•
main burners
fi
ring, disconnect thermocouple from
gas valve. Gas valve should immediately shut off
main burners and pilot.
RELIGHT
Electric and gas shall be off for 5 minutes before
relighting.
THERMOSTAT
Keep it set at desired room temperature. If windows
are to be opened or heat is not needed, move
thermostat pointer to lower setting.
NOTICE
In event of failure of any component, system
will not operate or will go into safety lockout.
System is completely self-checking. On
every call for heat, each component must
be functioning properly to permit operation.
Safety lockout system has to be reset by
turning thermostat to lowest setting for one
minute, then back to normal setting.
ADJUST PILOT BURNER
Pilot
fl
ame should surround 3/8” to 1/2” of the pilot
sensor. See Figure 16. If
fl
ame needs adjusting, do it
as follows:
Remove screw cover over pilot adjusting screw.
1.
Insert small screwdriver and adjust
fl
ame as
2.
needed. Turn screw counterclockwise to increase
fl
ame, clockwise to decrease.
Replace screw cover over pilot adjusting screw.
3.
MAIN BURNER(S)
Main burners do not require primary air
•
adjustment and are not equipped with primary air
shutters.
Main burner
fl
ames form sharp blue inner cones in
•
softer blue outer mantel, with no yellow.
Puffs of air from blowing on
fl
ame or stamping on
•
fl
oor will cause
fl
ames to turn orange momentarily.
This is not unusual. Remain still when observing
main burner
fl
ames.
If
fl
ame appearance is not correct, check main
•
burner ori
fi
ces, burner throat and
fl
ame ports for
dust and lint obstruction. It may be necessary
to remove rollout shield to observe main burner
fl
ames. Replace rollout shield after observation.
Refer to Figure 17.
Figure 17 - Burner
ADJUST LIMIT CONTROLS
Instructions for each control are included with
controls. Settings can be changed. Refer to
Appendix A page 27 for information.