8 - ELECTRICAL CONNECTIONS
A. Connect Room End Switch
•
turn power off to boiler;
• access terminal block
M2
;
• connect room end switch to terminals
6(R)-7(W)-
8(C)
; Do not apply dry voltage between 2 terminals.
Dry contact only.
• turn boiler power on;
• verify room end switch operates per end switch
manufacturer instructions.
NOTE:
maximum load allowed is 10 mA
Dry contact end switches from various manufacturers can be
attached to boiler control PCB.
FIGURE 8-4 End Switch Connections
8.6 Install Room End Switch
Install room end switch on inside wall. Do not install where it
will be influenced by drafts, hot or cold water pipes, lighting
fixtures, television, sun rays or near a fireplace.
Dry contact only - do not apply 24 volts between 6 and 7.
A
Room End
Switch
8.7 Optional Electrical Connections
A. 1K Ohm (1K
Ω) Outdoor Temperature Sensor
To connect this accessory, see figure 8-5, terminals 4-5, and
instructions supplied with
1K
Ω
sensor.
Note
Sensors used for this boiler are proprietary to
the manufacturer. Use of after market sensors
will diminish boiler performance.
FIGURE 8-5 Outdoor Sensor Connections
1K
Ω
B. Setting "Kt" Climate Curve
1.
Boiler automatically recognizes OAS sensor when wired to M2
terminal block. Display changes to show current default “
Kt
”
value (80). Note display value.
2.
When operating in CH mode, boiler setpoint is determined
by the
Kt
value selected and actual outside air temperature.
Refer to applicable °F (or °C) chart, (pg. 30) for setpoint
information.
• Select
Kt
range which will satisfy the desired boiler delivery
temperature based on outdoor temperature range expected
for your location. For example: if you need 176°F water
when the outside temperature is 20°F and colder, select 35
for your
Kt
setting.
• To change”default”
Kt
value on boiler control use
or
CH Heating buttons.
• Restrict the upper limit of the
Kt
curve by using Parameter
P16 to set the maximum boiler water temperature. P16
Default is 176°F.
3.
When OAS is installed, pressing
or
buttons will no
longer display boiler CH setpoint temperature. It now displays
the
Kt
value which can range from 10 to 90.
4.
When scrolling has stopped, boiler will automatically “SAVE”
value as new
Kt
default value and automatically return to CH
mode when no
Kt
adjustment activity is sensed.
Kt
values
can be changed in +/- 1 point increments.
5.
To return, to verify or change current
Kt
“default value,
depress one of the CH setpoint adjustment buttons (once),
or
, while in any heating or standby mode. Adjust
Kt
value to obtain desired comfort level.
240013354 REV B [09/15/2021]
Содержание MAC-115
Страница 2: ...MAC 205 ...
Страница 4: ...MAH 165 ...
Страница 77: ...73 APPENDIX A WIRING DIAGRAMS A 2 MODEL 125 Heat Only 240013354 REV B 09 15 2021 ...
Страница 78: ...74 APPENDIX A WIRING DIAGRAMS A 3 MODEL 165 Heat Only 240013354 REV B 09 15 2021 ...
Страница 79: ...75 APPENDIX A WIRING DIAGRAMS A 1 MODEL 115 Combi 240013354 REV B 09 15 2021 ...
Страница 80: ...76 APPENDIX A WIRING DIAGRAMS A 4 MODEL 150 Combi 240013354 REV B 09 15 2021 ...
Страница 81: ...77 APPENDIX A WIRING DIAGRAMS A 5 MODEL 205 Combi 240013354 REV B 09 15 2021 ...
Страница 82: ...78 NOTES 240013354 REV B 09 15 2021 ...
Страница 118: ...34 MODEL 125 Heat Only 125 HEAT ONLY WIRING DIAGRAM PN 240011430 REV P 09 15 2021 ...
Страница 119: ...35 MODEL 165 Heat Only 165 HEAT ONLY WIRING DIAGRAM PN 240011430 REV P 09 15 2021 ...
Страница 120: ...36 115 COMBI WIRING DIAGRAM MODEL 115 Combi PN 240011430 REV P 09 15 2021 ...
Страница 121: ...37 MODEL 150 Combi 150 COMBI WIRING DIAGRAM PN 240011430 REV P 09 15 2021 ...
Страница 122: ...38 MODEL 205 Combi 205 COMBI WIRING DIAGRAM PN 240011430 REV P 09 15 2021 ...
Страница 127: ...43 Low Water Cutoff Detail LOW WATER CUTOFF NO NO YES PN 240011430 REV P 09 15 2021 ...
Страница 132: ...48 3 FAULT SOLUTION SECTIONS PN 240011430 REV P 09 15 2021 ...
Страница 135: ...51 Parameter ID Changed From Changed To Date Reason PARAMETER CHANGE HISTORY PN 240011430 REV P 09 15 2021 ...