COMB
COMB
COMB
COMB
COMBUSTION
USTION
USTION
USTION
USTION AIR REQ
AIR REQ
AIR REQ
AIR REQ
AIR REQUIREMENTS
UIREMENTS
UIREMENTS
UIREMENTS
UIREMENTS
(MINIMUM SQUARE INCHES OPENING)
*****
UNCONFINED AREA
**
**
**
**
**
CONFINED AREA
OUTSIDE
INSIDE
OUTSIDE COMBUSTION AIR
MODEL
COMBUSTION COMBUSTION
VERTICAL
HORIZONTAL
NUMBER
AIR 1 SQ. IN
AIR 1 SQ. IN.
DUCTS
DUCTS
MGB
/5000 BTU/HR
/1000 BTU/HR
1 SQ. IN.
1 SQ. IN.
(SEE FIG. 4)
(SEE FIG. 3)
/4000 BTU/HR
/2000 BTU/HR
MGB 38
8
100
10
19
MGB 50
10
100
13
25
MGB 75
15
100
19
38
MGB 100
20
100
25
50
MGB 125
25
125
32
63
MGB 150
30
150
38
75
MGB 175
35
175
44
88
MGB 200
40
200
50
100
MGB 225
45
225
57
113
MGB 275
55
275
69
138
MGB 300
60
300
75
150
VENTILA
VENTILA
VENTILA
VENTILA
VENTILATION & COMB
TION & COMB
TION & COMB
TION & COMB
TION & COMBUSTION
USTION
USTION
USTION
USTION AIR
AIR
AIR
AIR
AIR
WARNING:
WARNING:
WARNING:
WARNING:
WARNING:
AIR OPENINGS TO COMBUSTION AREA MUST NOT BE
OBSTRUCTED. BY FOLLOWING THE INSTRUCTIONS BELOW, ADEQUATE
COMBUSTION AIR CAN BE MAINTAINED
***** Unconfined area:
A space whose volume is not less than 50 cubic feet per
1000 BTU per hour of all appliances installed in that space (cubic feet of space = height x
width x length).
**
**
**
**
** Confined area:
A space whose volume is less than 50 cubic feet per 1000 BTU
per hour of all appliances installed in that space (cubic feet of space = height x width x
length).
1. Ventilation of the boiler room must be adequate to provide sufficient air to properly
support combustion per the latest revision of the National Fuel Gas Code, ANSI Z223.1
section 5.3.
2. When a boiler is located in an unconfined space in a building or conventional construction
frame, masonry or metal building, infiltration normally is adequate to provide air for
combustion and ventilation. However, if the equipment is located in a building of unusually tight
construction (See the national Fuel Gas Code, Ansi Z223.1 section 1.7), the boiler area
should be considered as a confined space. In this case air for combustion and ventilation shall
be provided according to part 5 on page 5. If there is any doubt, install air supply provisions
in accordance with the latest revision of the National Fuel Gas Code.
3. When a boiler is installed in an unconfined space, in a building of unusually tight