Figure 2: Module installation 

Screw

4-24

screws

Module

Wall plate

Compatible

electrical box

 

Wiring 

Wire in accordance with NFPA 72 and CAN/ULC-S524. Be 
sure to observe the polarity of the wires as shown in the 
diagram. 

Specifications 

 

Communication line voltage 

Maximum 20.6 V peak-to-peak 

Current 

Standby 
Activated 

 
550 μA 

725μA 

Ground fault impedance 

10 kΩ 

Operating environment 

Temperature 
Humidity 

 
32 to 120° F (0 to 49° C) 
0 to 93% RH 

Storage temperature range 

–4 to 140° F (–20 to 60° C) 

Compatible electrical boxes 

North American 4 inch square x  
2-1/2 in. (64 mm) deep 2 gang box 
Standard 4 in. square box 1-1/2 in. 
(38 mm) deep 

Wire size 

12, 14, 16, or 18 AWG wire (2.5, 1.5, 
1.0, or 0.75 mm

2

)  (Sizes 16 and 18 

AWG are preferred) 

Device address 

01 to 63 (64 point control panel) 

01 to 126 (127 point control panel) 

Initiating device circuit (IDC) 

EOL resistor value 
Max. circuit resistance 
Max. circuit capacitance 

 
47 kΩ, (P/N: EOL-47) 

50 Ω (25 Ω per wire) 

0.1 μF 

Figure 3: Module wiring 

Typical NO

Waterflow Switch

47 

EOLR

k

47 

EOLR

k

SUP.

Style B (Class B)

[1] [2] [4] 

W/FLOW

Typical NO

Supervisory/

Tamper Switch

[3]

TB2

TB1

(+)

(+)

SLC

(+)

(  )

(  )

(  )

From 

previous 

device

To next 
device

SLC out (+)

SLC out

SLC in

SLC in (+)

(  )

(  )

 

[1] 

Maximum 25 Ω resistance per wire 

[2]  Maximum 12 AWG (2.5 mm

2

) wire; minimum 18 AWG (0.75 mm

2

) wire 

[3]  Refer to the control panel technical reference manual for wiring specifications 
[4] 

Maximum 10 VDC at 350 μA 

5. 

All wiring is power-limited and supervised 

6. 

This module will not support two-wire smoke detectors 

 