background image

© 2013 UTC Fire & Security. All rights reserved. 

1 / 2 

P/N 3101194 • REV 02 • REB 28JAN13 

 

E-IDCWS Analog Dual Input Waterflow/ 
Supervisory Module Installation Sheet 

Operation 

The module is an analog addressable device used to connect 
normally open waterflow alarm and supervisory initiating 
device circuits (IDCs) to a control panel. This module is 
designed for Class B circuit operation. 

The device address is set using the two rotary switches located 
on the front of the module. Two consecutive device addresses 
are required. The second device address is automatically 
assigned one number higher that the value set on the rotary 
switches. 

The module can operate in the following modes: 

Table 1: Module operation 

Operation  

Device type description 

Waterflow 

Alarm latching delayed: Configures the module for use 
with only nonretarded waterflow alarm switches. When 
the NO input contact of an initiating device is closed, an 
alarm is sent to the control panel, which after a 16 
second time delay, generates an alarm signal. 

Supervisory 

Supervisory active nonlatching US marketplace 

Supervisory active latching Canadian marketplace 

Nonlatching: Configures the module for normally open 
dry contact initiating devices. When the NO input 
contact of an initiating device is closed, a supervisory 
signal is sent to the control panel and the supervisory 
condition is not latched at the module. 

Latching: Configures the module for normally open dry 
contact initiating devices. When the NO input contact of 
an initiating device is closed, a supervisory signal is 
sent to the control panel and the supervisory condition 
is not latched at the module. 

LED operation 

The module provides a bicolor LED that shows its status. 

Normal: Green LED flashes 

Alarm/active: Red LED flashes 

Installation 

WARNINGS

 

• 

This module will not operate without electrical power. As 
fires frequently cause power interruption, you should 
discuss further safeguards with your local fire protection 
specialist. 

• 

This module does not support conventional smoke 
detectors. 

Note: 

The module is shipped from the factory as an assembled 

unit; it contains no user-serviceable parts and should not be 
disassembled. 

To install the module: 

1.  Verify that all field wiring is free of opens, shorts, and 

ground faults. 

2.  Make all wiring connections as shown in “Wiring.” 

3.  Set the module address as follows: 

Use a screwdriver to adjust the two rotary switches on the 
front of the module. Set the TENS rotary switch (0 through 
12) for the 10s and 100s digit and the ONES rotary switch 
for the 0 through 9 digit. For example: device address 21, 
set TENS rotary switch to 2 and set the ONES rotary 
switch to 1. 

Refer to “Specifications” for available address numbers. 

Mount the module on the electrical box using screws 
provided with the electrical box. 

5.  Mount the wall plate on the module using #4-24 x 1/2 in.  

(13 mm) self-tapping screws. 

Figure 1: Module address 

Insert

screwdriver

here

 