UTC Fire and Security EDWARDS 250-CO SafeAir Скачать руководство пользователя страница 5

P/N 1061018 • REV E • ISS 14JUL11 

 

5 / 8 

Figures 

Figure 1: 250-CO 

Figure 2: Detector locations 

  Recommended CO detector location 

Figure 3: 250-CO components 

(1) Alarm 

relay 

(2) Terminals 

” and “+” are for power; terminals “NO” (normally 

open) and “C” (common) are the common trouble relay shown in 
the normal state for this detector 

(3) Sensor 
(4) Sounder 

Figure 4: Single device, single zone configuration 

(1)  Power (see Specifications) 
(2)  Alarm initiating device circuit (IDC) (normally open) 
(3)  End-of-line device (provided by the life safety system) 

Note: Relay is shown in the normal state for this detector. 

Figure 5: Multiple devices, single zone configuration 

(1)  Power (see Specifications) 
(2)  Alarm IDC (normally open) 
(3)  End-of-line device (supplied by life safety system) 

Note: Relay is shown in the normal state for this detector. 

Figure 6: Multiple devices, separate alarm, trouble zone 
configuration 

(1)  Power (see Specifications) 
(2)  Alarm IDC (normally open) 
(3)  Supervisory IDC (normally open) 
(4)  End-of-line device (provided by the life safety system) 

Note: Relay is shown in the normal state for this detector. 

Figure 7: 250-CO features 

(1) Test/hush 

button 

(2) Sensor 

port 

Installation 

WARNING: 

Potential loss of life. Failure to properly  install, 

test, and maintain a CO detector may cause it to fail. Connect 
the CO detector only to a zone that is dedicated exclusively to 
CO detection and that is monitored 24 hours a day. Do not 
connect to an initiating circuit with fire or security devices. 

The 250-CO SafeAir Carbon Monoxide Detector is a four-wire 
device designed to use a Class 2 output from a control panel 
listed to the ANSI/UL 985 or 864 standards or auxiliary power 
supply. 

All wiring must conform to the NFPA 70 

National Electric Code

ANSI/UL 2075 

Standard for Gas and Vapor Detectors and 

Sensors

, NFPA 720 

Standard for the Installation of Carbon 

Monoxide

 

(CO) Detection and Warning Equipment

, applicable 

codes, and the local AHJ.

 

The 250-CO SafeAir Carbon Monoxide Detector is intended for 
indoor-dwelling unit applications in both residential and 
commercial occupancies, including single/multiple family 
residential occupancies, hotel rooms, dorm rooms, and other 
areas approved by the authority having jurisdiction (AHJ). 

The 250-CO detector can connect to either UL 985 (Household 
Fire Warning) or UL 864 (Commercial Fire) control panels. It is 
not intended for use in industrial applications such as gasoline 
refineries or parking garages, which require different listings. 

The 250-COPLT adapter plate 

The 250-CO detector has an optional adapter mounting plate. 
Use the 250-COPLT adapter plate when replacing a 240-COe 
with a 250-CO to cover the footprint of the 240-COe. To 
purchase the plate order P/N 250-COPLT-5PKG. 

To install the detector without using the adapter plate: 

1.  Run the 250-CO detector wiring to the detector location. 

2.  Carefully remove the cover from the detector using a 

small, flat screwdriver blade in the slot on the left side of 
the detector cover. 

3.  The mounting hole pattern is for single-gang spacing. Use 

the base for a template to mark the two screw hole 
locations on the mounting surface or mount on a single-
gang box (not provided). The unit can be mounted 
vertically or horizontally. 

4.  Install two screws on the marks. If necessary, use wall 

anchors. 

5.  Line up the base with the screws, pull the wires through 

the square holes, and then slide the base over the screws. 
For surface wiring, pull the wires through the wiring 
channel at the bottom of the base. 

6.  Strip 3/8 in. of insulation from each wire. 

7.  Determine the correct wiring, and then insert the wires 

under the appropriate screw terminals. See "Wiring" and 
Figure 4 to Figure 6. 

8.  Tighten both screws to secure the base to the wall. 

9.  Replace the detector cover. 

10.  Apply power. The LED should flash green for 

approximately four seconds, and then pulse green. 

11.  Test in accordance with “Testing” on page 6. 

To install the detector using the adapter plate: 

1.  Run the 250-CO detector wiring to the detector location. 

2.  Using the 250-COPLT wall plate for a template, trace the 

perimeter of the two square holes on the mounting 
surface. Also mark the two screw locations. 

3.  Cut out the two square holes. 

4.  Install two screws on the marks. If necessary, use wall 

anchors. 

5.  Mount the wall plate but do not fully tighten the screws. 

6.  Carefully remove the cover from the detector using a 

small, flat screwdriver blade in the slot on the left side of 
the detector cover. 

7.  Pull the wires through the square holes on both the wall 

plate and the 250-CO base. Then slide the detector base 
over the screws. 

firealarmresources.com

Содержание EDWARDS 250-CO SafeAir

Страница 1: ... 2011 UTC Fire Security All rights reserved 1 8 P N 1061018 REV E ISS 14JUL11 250 CO SafeAir Carbon Monoxide Detector Installation Sheet 1 2 3 4 3 1 2 4 3 2 1 5 1 2 3 firealarmresources com ...

Страница 2: ...ectly for more information about CO safety for the equipment Make sure that motor vehicles are not and have not been operating in an attached garage or adjacent to the premises Information about carbon monoxide WARNINGS Read these installation instructions in their entirety before proceeding Leave these instructions with the owner user of this CO detection equipment This product is intended for us...

Страница 3: ...tions in vent pipes or unconventional vent pipe designs which can amplify the above situations Poorly designed or maintained chimneys and or vents Extended operation of unvented fossil fuel burning devices range oven fireplace etc Idling cars in an open or closed attached garage or near the premises General limitations of CO detectors This detector is designed to protect individuals from the acute...

Страница 4: ...flashing amber LED and intermittent sounder chirps to indicated that the detector needs replacing The detector also signals a trouble condition when the CO sensor reaches end of life As soon as possible replace a detector that reaches end of life because it may no longer detect carbon monoxide accurately Common trouble relay When connected to a listed control panel the trouble relay can report a t...

Страница 5: ...on AHJ The 250 CO detector can connect to either UL 985 Household Fire Warning or UL 864 Commercial Fire control panels It is not intended for use in industrial applications such as gasoline refineries or parking garages which require different listings The 250 COPLT adapter plate The 250 CO detector has an optional adapter mounting plate Use the 250 COPLT adapter plate when replacing a 240 COe wi...

Страница 6: ...or 10 days or more Test the detector by pushing the test button after installation and once a week to verify that it is functioning properly If the detector fails the test verify all connections wait briefly then try again If the detector fails again replace it Notify all persons and facilities that receive alarm and trouble signals before beginning the test to prevent unnecessary response To test...

Страница 7: ...uminates approximately 2 seconds Waiting five minutes until the unit automatically exits out of the fast CO test mode Specifications Input voltage 12 or 24 VDC supplied by control panel or resettable auxiliary power supply Current consumption Normal Alarm 20 mA 40 mA 75 mA in test Alarm relay Type UL rating 150 mA at 33 VDC Form C Zone Common trouble relay Type UL rating 150 mA at 33 VDC Normally ...

Страница 8: ...8 8 P N 1061018 REV E ISS 14JUL11 firealarmresources com ...

Отзывы: