SYSTEM CHECKOUT

A system checkout should be performed after 
installation is complete.  A periodic maintenance 
checkout (with minimum frequency of once every six 
months) should be scheduled to ensure that the system 
is in proper operating condition.  Depending on the 
degree of hazard and the amount of contaminants in 
the atmosphere, the checkout can be scheduled more 
often.  Note that oil films will significantly reduce the 
transmission of ultraviolet radiation through the detector 
windows.

For specific system checkout instructions, see the 
“Checkout Procedure” section of the instruction manual 
for the flame detection system being used.

The W867 Test Lamp is a safe, portable UV/IR source 
for external testing and verification of the response 
of Det-Tronics UV, single frequency IR, and UV/IR 
detectors.  It is suitable for use in hazardous (classified) 
areas, but is not a substitute for an actual open flame 
test.

SERVICE PROCEDURES

BATTERY MAINTENANCE

A battery charge level indicating LED and the charger 
cable connection for recharging the battery are located 
beneath a removable windowed plug in front of the 
ON pushbutton switch.  See Figure 2.  To maintain the 
explosion-proof rating of the W867, the plug must be 
installed whenever the battery is not being charged.  
To determine the battery charge level, press the ON 
pushbutton and observe the Indicating LED.  When the 
battery is fully charged, the red Indicating LED (viewed 
through the window) is off.  When the battery reaches 
a marginal level, the Indicating LED will flash on and 
off.  The battery should be recharged at this time.  If 
the Indicating LED is on continuously, the battery is at a 
very low level and the test lamp should not be operated 
until the battery has been recharged.  

WARNING

The life of the battery is significantly reduced 
if it is operated when the red LED is on 
continuously.

RECHARGING

A 12 volt dc, 0.3 ampere battery charger is provided 
to supply dc voltage from an ac outlet for recharging 
the W867 battery.  Battery chargers are available to 
operate on either 120 vac 60 Hz or 220 vac 50 Hz 
(optional).  This plug-in battery charger contains a 
Power On LED to indicate when the charger is plugged 
in and a Fast Charge LED to indicate when the battery 
is being charged.  

WARNING

Do not operate the W867 Test Lamp when the 
battery is charging.  

Do not recharge the battery in a hazardous area.

To recharge the battery, first remove the windowed plug 
to gain access to the recharge connection.  Plug the 
charger cable plug into the battery.  Plug the battery 
charger into the appropriate ac outlet.  The Power On 
and Fast Charge LEDs on the battery charger should 
be on.  When the battery is fully charged, the Fast 
Charge LED will go out.  This should take from 12 to 14 
hours from a discharged state.

To return the W867 Test Lamp to service, unplug the 
battery charger from the ac outlet.  Disconnect the 
charger cable from the battery.  Replace the windowed 
plug.  Press the ON pushbutton and observe the 
indicating LED on the battery.  The indicating LED 
should be off, which shows that the battery is fully 
charged and ready to operate.  

Содержание Det-Tronics W867

Страница 1: ... 1 Groups E F and G For storage and use in dry or damp locations only ELECTRICAL RATINGS Battery Charger Input Voltage 120 volts ac 60 Hz 220 volts ac 50 Hz optional TEMPERATURE RANGE Operating 5 F to 122 F 15 C to 50 C Charge 32 F to 104 F 0 C to 40 C Storage 5 F to 104 F 15 C to 40 C OPERATING TIME Approximately 15 minutes continuous between recharges This will vary with the ambient temperature ...

Страница 2: ... It may be necessary to decrease the distance between the detector and the test lamp in order to obtain a response Do not operate the test lamp longer than is necessary to actuate the detector Each detector can be checked with less than 30 seconds of operating time It is important to avoid discharging the battery to the point where the battery charge level Indicating LED see Figure 2 is on steady ...

Страница 3: ...window is off When the battery reaches a marginal level the Indicating LED will flash on and off The battery should be recharged at this time If the Indicating LED is on continuously the battery is at a very low level and the test lamp should not be operated until the battery has been recharged WARNING The life of the battery is significantly reduced if it is operated when the red LED is on contin...

Страница 4: ...equipment transportation prepaid to the factory in Minneapolis ORDERING INFORMATION When ordering specify Part Number Description 004000 003 W867C3001 120 VAC 004000 004 W867C3002 220 VAC 2 pin Euro 004000 005 W867C3003 220 VAC 3 pin UK NOTE Includes test lamp with battery and charger For assistance in ordering please contact Detector Electronics Corporation 6901 West 110th Street Minneapolis Minn...

Отзывы: