12
95-8562
3.2
12
95-8562
A
pp
ENDIX
D
NONINCENDI
v
E
C
l
A
SS
B,
S
T
yl
E
B
WIRIN
g
Hazar
dous
(Classifi
ed)
l
ocations:
Class
I,
Division
2,
g
roup
A,
B,
C,
D
Class
II,
Division
2,
g
roup
F,
g
Class
III,
Division
2
Non-hazar
dous
(Non-c
lassifi
ed)
l
ocations
F
igur
e
D1—Non-Incendiv
e
Class
b
,
St
yle
b
W
iring
(Dr
awing
No
. 420033)
PM-5MPX
PM-5MPX
PM-5MPX
V+ (RED)
V+ (ORG)
PWR RTN (BLK)
PWR RTN (BRN) ALARM + (YEL) ALARM + (GRN) ALARM – (BLU) ALARM – (VIO) T (GRY) TROUBLE – (WHT)
V+ (RED) V+ (ORG)
PWR RTN (BLK) PWR RTN (BRN)
ALARM + (YEL) ALARM + (GRN) ALARM – (BLU) ALARM – (VIO) T (GRY) TROUBLE – (WHT)
V+ (RED) V+ (ORG)
PWR RTN (BLK)
PWR RTN (BRN)
ALARM + (YEL)
ALARM + (GRN)
ALARM – (BLU) ALARM – (VIO) T (GRY) TROUBLE – (WHT)
END OF LINE
DEVICE
CONTROL ROOM INSTRUMENTATION
+24 VDC
DC RETURN
ALARM +
ALARM –
HAZARDOUS LOCA
TION:
CLASS I, DIV
. 2, GROUPS
A, B, C & D.
CLASS II, DIV
. 2, GROUPS F & G.
CLASS III, DIV
. 1 & 2.
NON-HAZARDOUS LOCA
TION
PM-5MPX
ELECTRICAL
INTERF
ACE
Wire
Color
Signa
l
Red
V+,
Input
Power
Orange
V+,
Input
Power
Black
Power
Return
Brown
Power
Return
Yellow
Alarm
+
Green
Alarm
+
Blue
Alarm
–
Violet
Alarm
–
Gray
Trouble
+
White
Trouble
–
NOTES:
1.
FOR
INST
ALLA
TION
IN
NONINCENDIVE,
CLASS
I,
DIVISION
2,
GROUPS
A,
B,
C
&
D;
CLASS
II,
DIVISION
2,
GROUPS
F
&
G;
CLASS
III,
DIVISION
2
HAZARDOUS
(CLASSIFIED)
LOCA
TIONS,
OR
NON-
HAZARDOUS
LOCA
TIONS
ONL
Y.
W
IRING
METHODS
SHALL
BE
INST
ALLED
IN
ACCORDANCE
WITH
ANSI/NFP
A
70
(NEC)
A
RT
ICLE
501-4(b)
AND
ANSI/NFP
A
72.
2.
THIS
DRA
WING
SHOWS THREE
SENSORS
CONNECTED
IN
ONE
ZONE
IN
A
CLASS
B,
STYLE
B
CONFIGURA
TION
PER
NFP
A
72.
ADDITIONAL
SENSORS
CAN
BE
ADDED
BY
REPEA
TING THE
WIRING
PA
TTERN
OF THE
CENTRAL
SENSOR.
3.
PM-5MPX
INTERCONNECTS
VIA
FL
YING
LEAD.
4.
ELECTRICAL
REQUIREMENT
:
9
T
O
30
VDC
AND
10
MILLIAMPS
(MAX)
PER
SENSOR.
5.
AN
END
OF
LINE
DEVICE,
AS
REQUIRED
BY
THE
FIRE
ALARM
CONTROL
PANEL,
IS
USED
TO
MONIT
OR
LINE
CONTINUITY
.