1. Use a minimum 3-1/2" thick brick masonry wall framed into the combustible wall.  A fireclay liner (ASTM C315 or equivalent) having 

a 5/8" minimum wall thickness must be used and it must be at least 12" away from any material that could catch fire.  The inside 

diameter of the fireclay liner shall be sized for the proper snug fit of a 6" diameter  chimney connector pipe. The fireclay liner shall 

run from the outer surface of the brick wall to, but not beyond, the inner surface of the chimney flue and shall be firmly cemented 

in place. See Part A.

MINIMUM 12 IN.

TO COMBUSTIBLES

FIGURE 12, PART A

C

H

IM

N

E

Y

 F

LU

E

MINIMUM CHIMNEY CLEARANCE TO

BRICK AND COMBUSTIBLES IS 2 IN.

MINIMUM CLEARANCES 12 IN.

OF BRICK ALL AROUND

CHIMNEY  CONNECTOR

TO HEATER

FIRE CLAY LINER

(5/8" MIN. WALL THICKNESS)

MIN. 3-1/2" THICK BRICK

MASONRY WALL

MASONRY CHIMNEY

CONSTRUCTED TO

NFPA 211

FIGURE 12, PART B

AIR SPACE

9 IN. MINIMUM

FACTORY-BUILT

CHIMNEY LENGTH

MINIMUM CHIMNEY CLEARANCES FROM MASONRY TO

SHEET STEEL SUPPORTS AND COMBUSTIBLES 2 IN.

CHIMNEY LENGTH

FLUSH WITH INSIDE

OF FLUE

NONSOLUBLE

REFACTORY

CEMENT

MASONRY CHIMNEY CONSTRUCTED

TO NFPA 211

CHIMNEY CONNECTOR

TO HEATER

MINIMUM CLEARANCE

9 IN.  ALL AROUND

SHEET STEEL SUPPORTS

(24 GAUGE MIN. THICKNESS)

CHIMNEY

 FLUE

SOLID INSULATED, LISTED

FACTORY-BUILT CHIMNEY LENGTH

USE CHIMNEY MFRS. PARTS TO

ATTACH CONNECTOR SECURELY

AIR SPACE

2. Use a solid insulated listed factory-built chimney length having an inside diameter of 6" and having 1" or more of solid insulation.  

There must be at least a 9" air space between the outer wall of the chimney length and any  combustible materials.  The inner end 

of the chimney length shall be flush with the inside of the masonry chimney  flue and shall be sealed to the flue and to the brick ma-

sonry penetration with nonwater-soluble refractory cement. Sheet steel supports which are at least 24 gauge (0.024") in thickness 

shall be securely fastened to wall surfaces on  all sides.  Fasteners between supports and the chimney length shall not penetrate 

the chimney liner. See Part B.

TWO VENTILATED AIR

CHANNELS EACH 1 INCH.

CONSTRUCTED OF

SHEET STEEL.

FIGURE 12, PART C

MASONRY CHIMNEY CONSTRUCTED

TO NFPA 211

SHEET STEEL SUPPORTS

(24 GAUGE MIN. THICKNESS)

MINIMUM CHIMNEY CLEARANCES FROM MASONRY TO

SHEET STEEL SUPPORTS AND COMBUSTIBLES 2 IN.

MINIMUM 6 IN. GLASS

FIBER INSULATION ALL AROUND

24 GAUGE

VENTILATED THIMBLE WITH

TWO 1 INCH AIR CHANNELS

CHIMNEY THIMBLE

CHIMNEY

 FLUE

CHIMNEY CONNECTOR

TO HEATER

3. Use a 10" diameter ventilated thimble made of at least 24 gauge (0.024") steel having two 1" air channels.  The ventilated thimble 

must be separated from combustible materials by a minimum of 6" glass fiber insulation.  The opening  in the combustible wall shall 

be covered and the thimble supported with sheet steel supports which are at least 24 gauge (0.024") in thickness.  The sheet steel 

supports shall be securely fastened to wall surfaces on all sides and shall be sized to fit and hold the chimney section.  Fasteners 

used to secure chimney sections shall not penetrate chimney flue liner.  See Part C.

Содержание Hotblast 1557M

Страница 1: ...NUAL SOLID FUEL WARM AIR FURNACE FOR PARALLEL INSTALLATION WITH EXISTING FORCED AIR GAS OR OIL FIRED FURNACE U S ONLY FOR INSTALLATION AS A CENTRAL FURNACE ALL MODELS CERTIFIED UNDER UL 391 85591T CAUTION READALLINSTRUCTIONSCARE FULLY BEFORE STARTING THE INSTALLATIONOROPERATING THE FURNACE IMPROPER INSTALLATION MAY VOID YOUR WARRANTY DO NOT USE THIS FURNACE IN A MOBILE HOME OR TRAILER ...

Страница 2: ... Foot Folding Rule or Tape Tin Snips Drill Hand or Electric Drill Bit 1 8 Dia For Sheet Metal Screws Screw Driver Blade Type Gloves Sabre Saw 5 16 Nut Driver or 5 16 Socket w Ratchet Safety Glasses MATERIAL 6 Pipe 6 Elbow Collar and Thimble as required 24 gauge min 1 2 Sheet Metal Screws 6 Inside diameter Listed Residential Type or Building Heating Appliance Chimney or existing masonry chimney Ele...

Страница 3: ...on SAFETY NOTICE If this heater is not properly installed a house fire may result For your safety follow the installation directions Contact local building or fire of ficials about restrictions and installation inspection requirements in your area If not already installed we recommend that smoke detectors be installed CAUTION CLEANOUT OF THE HEAT EXCHANGER FLUE PIPE CHIMNEY AND DRAFTINDUCER IFUSED...

Страница 4: ...g Appliances NFPA 211 The address of the NFPA is Batterymarch Park Quincy MA 02269 11 Keep the ashpit section free of excess ashes Do not allow ashes to stack higher than the sides of the ash pan 12 DISPOSAL OF ASHES Place ashes in a metal container with a tight fitting lid Keep the closed containeronanoncombustiblefloororontheground well away from all combustible materials Keep the ashes in the c...

Страница 5: ...FURNACE INSTALLATION As a central furnace the unit functions indepen dently of any other system The blower will come on when the plenum temperature reaches the setting on the blower control HOW THE FURNACE FUNCTIONS PARALLEL INSTALLATION U S ONLY The design is such that when the blower comes on the blower on the central system also comes on The blower will only come on when the tem perature in the...

Страница 6: ...6 DIMENSIONS OF FURNACE Figure 2 Model 1557M Figure 1 Model 1357M ...

Страница 7: ...stible sur faces If you have a solid brick or stone wall behindyourfurnace youcanplacethefurnace as close as you wish to the wall If the wall is only faced with brick or stone treat it as a combustible wall 18 18 6 SOLID DAMPER 6 BAROMETRIC DRAFT REGULATOR NON COMBUSTIBLE FLOOR 12 9 48 18 CENTRAL FURNACE 6 CHIMNEY 21 Figure 4 Figure 5 1357M 1557M Unit to Sidewall 12 305mm 12 305mm Unit to Backwall...

Страница 8: ...chimney dealer Theinstallationmustconformtolocalfirecodes and N F P A 211 DO NOT CONNECT THIS FURNACE TO A CHIMNEY FLUE SERVING ANOTHER APPLIANCE Thechimneyusedforafurnacemustnotbeused to ventilate the cellar or basement If there is a cleanout opening at the base of the chimney close it tightly LISTED FACTORY BUILT CHIMNEY Carefullyfollowchimneymanufacturer sinstruc tions Use only a Listed Residen...

Страница 9: ...om same pressure zone as the furnace 8 Install the barometric draft regulator strictly in ac cordance with the instructions that are provided with the barometric draft regulator 9 Asolid damper must be used in the chimney connect ing pipes between the flue collar and the chimney When used in conjunction with a barometric draft regulator the solid damper must be placed between the barometric and th...

Страница 10: ...ow to connect the chimney connector of a heater to a masonry chimney through a combustible wall There are five allowable ways that a chimney connector can be connected to a masonry chimney by passing through a combustible wall NFPA Standard 211 allows the following wall pass through systems Figure 11 ...

Страница 11: ...an inside diameter of 6 and having 1 or more of solid insulation There must be at least a 9 air space between the outer wall of the chimney length and any combustible materials The inner end of the chimney length shall be flush with the inside of the masonry chimney flue and shall be sealed to the flue and to the brick ma sonry penetration with nonwater soluble refractory cement Sheet steel suppor...

Страница 12: ... shown for 3 and 4 above Parts C and D shall be for types 3 and 4 connections to facilitate removal of the chimney connector for cleaning The chimney thimble shall be of ASTM C315 fireclay with 5 8 minimum wall thickness or material or equivalent durability The inside diameter of the thimble shall be sized for the proper snug fit of a 6 diameter chimney connector pipe The thimble shall be installe...

Страница 13: ... Figure 14 withscrewsandnutsprovided Note Slottedholes are for adjustment of handle Adjust handle until some pressure is required to lock feed door during firing sequence 4 Install the thermodisc on rear of furnace cabinet with the two screws provided Mount the conduit assembly from the junction box to the thermostat bracket Crimp the two female terminals to each of the wire leads Plug the wires t...

Страница 14: ... wiring wires M1 M2 of one blower motor Wire leads from the distribution blower are usually BOTH BLACK Makes no difference which leads from the motor s connects to the corresponding leads coming out of the conduit Figure 16 WIRING DIAGRAM ...

Страница 15: ...ue gases b Locate the Wood or Coal Burning Furnace as close as practical to the existing central hot air heatingsystem maintainingclearancesasstated on the label on the fuel door c Clearancefromcombustiblematerialsmustcom ply with those stated on the label on the side of the unit Refer to the clearance table in the front of this manual The installation must be made only on a noncombus tible floor ...

Страница 16: ...rs or soot in the chimney 1 Set thermostat to HIGH before opening feed door 2 Wood fire Add wood to a convenient level 3 Coal Fire a Never smother the fire when adding coal Gases from the accumulation smoke will explode under certain conditoins Add fresh kindling if the bed of coals has cooled b Add up to 20 lbs of coal per loading Never add coal above the bottom of feed door opening c Stir the co...

Страница 17: ...esiduewhich accumulates on the flue lining When ignited this soot makes an extremely hot fire The chimney should be inspected at least twice monthly during the heating season to determine if a creosote or soot build up has occurred If creosote or soot has accumulated it should be removed to reduce the risk of a chimney fire Chimney fires burn very hot If the chimney catches fire immediately call t...

Страница 18: ...pipe to chimney Your unit should be within six 6 feet of your chimney C Make sure chimney cap is not too close to the top of the chimney D Check chimney draft make sure chimney flue pipe is clean and chimney is of adequate height E Makesureyou renotsuffocatingthefirewithexces sive amounts of unburned wood F Slide baffle should be pulled out prior to load door opening 4 Problem Distribution blower ...

Страница 19: ...19 Repair Parts 22 6 8 7 9 20 18 19 17 16 14 10 15 11 12 13 21 1 5 2 3 4 1 28 27 26 29 30 31 24 25 32 33 23 35 34 38 37 36 40 38 36 37 39 34 42 41 46 48 47 44 43 45 49 1357M 1557M 69399 ...

Страница 20: ...398 1557M 2 23 22761B Flue Collar Ring 1 24 22762B Forced Draft Ring 1 25 86402 1 1 2 Pipe Plug 1 26 80230 Blower 1357M 1 1557M 2 27 89319 Gasket Blower 1357M 1 1557M 2 28 83340 1 4 20 Clipnut 1357M 4 1557M 8 N S 83339 Bolt 1 4 20 x 3 4 1357M 4 1557M 8 29 22140 Relay Box Bracket 1 30 80131 Junction Box 4 x 4 1 31 80231 Junction Box Cover 1 32 80314 Thermodisc 60T12 1 33 68234 Blower Thermostat Bra...

Страница 21: ...uses a standard 16 x 20 x 1 filter NOT INCLUDED to reduce the amount of dust particles from being transfered thru you duct work system DR 6 Barometric Damper Regulator In the unlikely event that your furnace overfires a con dition evidenced by elbows stove pipes and connectors glowing red in appearance or otherwise discoloring then your installation is subject to excessive draft cre ated by either...

Страница 22: ...coals start adding coal in layers allowing each to ignite before adding more Bituminous has a high volatile content and as a re sult should be fired with the conical method with the highest portion of your fire bed in the center of the firebox The first flames will be long and gen erally orange or yellow and produce quite a bit of smoke As the gases burn off the flames become shorter change color ...

Страница 23: ...he fire too much Next add a fresh charge to the back being careful not to seal off the top Close the feed door but leave the spin damper or thermostat open for a few minutes until the volatile gases have burned off It is not necessary to shake down the ashes each time you refuel the furnace Experience will be your best teacher Bulletin rc454 a guide to Burning coal in your furnace BANKING THE FIRE...

Страница 24: ...24 CENTRAL INSTALLATION ADD ON INSTALLATION ...

Страница 25: ... RETURN TO EXISTING DUCT WORK WARM AIR EXISTING FURNACE SOLID FUEL FURNACE FILTER BOX PLENUM COLLECTOR BOX COLD AIR RETURN TO EXISTING DUCT WORK WARM AIR EXISTING FURNACE SOLID FUEL FURNACE FILTER BOX COLD AIR RETURN PLENUM TOP OPTIONAL Appendix INSTALLATION A INSTALLATION B INSTALLATION C ...

Страница 26: ...26 INSTALLATION D INSTALLATION E ...

Страница 27: ...27 INSTALLATION H TOP VIEW FRONT VIEW INSTALLATION F INSTALLATION G ...

Страница 28: ...which is on the nameplate attached to the heater When ordering repair parts always give the following infor mation as shown in this list 1 The part number 2 The part description 3 The model number 1357M 1557M 4 The serial number ____________________ How to order repair parts United States Stove Company 227 Industrial Park Road P O Box 151 South Pittsburg TN 37380 800 750 2723 WWW USSTOVE COM C S S...

Отзывы: